Figure 2. Point Capture Wiring
•
Refer to Programming section on how to configure BAT-Fire’s PGM1, PGM2, and PGM3 for FACP
panel point capture and PGM4 as a trouble trigger. PGM4 is an open-collector output.
•
This figure shows one possible configuration between BAT-Fire and the FACP/burg panel. A relay
may not be required. Refer to your FACP/burg panel installation manual. If a relay is required, use a
UL 864 or ULC-S527 listed relay (i.e. Fire-Lite
®
PAM-2 by Honeywell
®
relay).
• The panel must support the relay contacts as indicated above (NC for alarm and AC-FAIL and NO
for Trouble) and battery calculation shall consider the additional current draw into the PGM’s during
the Normal Standby state.
• Use 4.7k ohm 1/4 Watt minimum resistors (not included).
• PGM ports are not supervised.
• Only panels without supervisory signaling can use this setup.
•
For UL 864 10th edition, this configuration may only be used for panels with one input zone. 9th
edition and earlier permitted this method for multiple protection zones.
• PGM1, PGM2, and PGM3 are not to be used as alarm and trouble inputs in commercial burg
applications.