Table 1: PARAMETERS FOR UL 864 & UL 1610 COMPLIANCE (USA)
NOTICE TO INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED
PARTIES:
This product incorporates field-programmable software. All features/options described below
are permitted in UL 864/UL 1610. In order to comply with the requirements in the Standard
for Control Units and Accessories for Fire Alarm Systems, UL 864, and/or Standard for Central-
Station Burglar-Alarm Units, UL 1610, certain programming features or options must be limited
to permitted settings or not used at all as indicated below.
Program
Feature or
Option
Situation
Possible
Settings
Default
Settings
UL 864
Required
Settings
UL 1610
Required
Settings
Notes
Supervision
Preference
(Comm Trouble
Supervision)
IP with Cell
Backup
60 seconds -
6 hours
6 hours
6 hours or
shorter
Primary: 200
seconds
or shorter
Backup: 6 hours
For UL 1610, if the
primary path fails,
system supervises
secondary path
at the primary
interval.
Sole Path IP
60 seconds -
6 hours
1 hour
1 hour or
shorter
200 seconds or
shorter
Turn off cellular
supervision
Turn off virtual
interface
supervision for
both primary and
backup cellular
Sole Path
Cell
60 seconds -
6 hours
1 hour
1 hour or
shorter
200 seconds or
shorter
Turn off Ethernet
supervision
Turn off virtual
interface
supervision for
both primary and
backup Ethernet
Remote
Programming*
On-site or
Remote
Enabled or
Disabled
Disabled
Disabled
Enabled or
Disabled
If Disabled,
Installer must
press Config
button onsite
Phone 2 Trouble
Trigger
If using
Phone Line
capture
(Figure 1)
Power Fail
Cover Tamper
Cell Fail
Ethernet Fail
CS Fail
CS Trouble
CS Fail
CS Fail**
Cover Tamper**
CS Fail
Figure 1:
Any Enabled
Trouble: BAT-Fire
drops Phone 2
line voltage
PGM4 Port
Trouble Trigger
If using Point
Capture
(Figure 2)
Power Fail
Cover Tamper
Cell Fail
Ethernet Fail
CS Fail
CS Trouble
CS Fail
CS Fail**
Cover Tamper**
CS Fail
Figure 2:
BAT-Fire PGM4
Output
(Any Enabled
Trouble)
connected to
FACP/burg panel
Trouble Input
* If Remote Programming is disabled, updates to site-specific parameters and BAT-Fire firmware are only permitted when the Config
button on the BAT-Fire is pressed for 2 seconds.
** These trouble triggers are required to meet the UL864 and UL1610 standards. However, all other trouble triggers listed in the Possible
Settings column are permitted.
• If Commercial Burg is selected, the more restrictive of the Fire and Burg timings will be used.
• Earlier editions of NFPA require supervision settings of 5 minutes.
•
UL 864 10th edition permits the point capture configuration for FACPs/burg panels protecting only a single zone; the 9th edition permits
point capture for multi-zone FACPs/burg panels.
• UL1610 requires 128 bit encryption or better. For active communications, the encryption shall be enabled at all times.