Table 2: PARAMETERS FOR ULC-S559 & ULC-S304 COMPLIANCE (CANADA)

NOTICE TO INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED 

PARTIES:

This product incorporates field-programmable software. All features/options described below 

are permitted in ULC-S559/ULC-S304. In order to comply with the requirements in the Standard 

for Equipment for Fire Signal Receiving Centres and Systems, ULC-S559-13-R2018 and/or the 

Standard for Control Units, Accessories and Receiving Equipment for Intrusion Alarm Systems, 

ULC-S304:2016-REV1, certain programming features or options must be limited to permitted 

settings or not used at all as indicated below.

Program 

Feature or 

Option

Situation

Possible 

Settings

Default 

Settings

ULC-S559 

Required 

Settings

ULC-S304 

Required 

Settings

Notes

Supervision 

Preference 

(Comm Trouble 

Supervision)

IP with Cell 

Backup

60  seconds  -         

6 hours

6 hours

Primary: 180 

seconds 

or shorter  

Backup: 6 

hours

Primary: 180 

seconds or 

shorter

    Backup: 6 

hours

For ULC-S559, if 

primary path fails, 

system supervises 

secondary path 

at the primary 

interval.

Sole Path IP

60 seconds -        

6 hours

1 hour

180 seconds 

or shorter

180 seconds or 

shorter

Turn off cellular 

supervision

Turn off virtual 

interface 

supervision for 

both primary and 

backup cellular

Sole Path 

Cell

60 seconds -        

6 hours

1 hour

180 seconds 

or shorter

180 seconds or 

shorter

Turn off Ethernet 

supervision 

Turn off virtual 

interface 

supervision for 

both primary and 

backup Ethernet

Remote 

Programming*

On-site or 

Remote

Enabled or 

Disabled

Disabled

Enabled or 

Disabled

Enabled or 

Disabled

If Disabled, 

Installer must 

press Config 

button onsite

Phone 2 Trouble 

Trigger

If using 

Phone Line 

capture

(Figure 1)

Power Fail

Cover Tamper

Cell Fail

Ethernet Fail

CS Fail

CS Trouble

CS Fail

CS Fail**

Cover Tamper**

CS Fail

Figure 1:

Any Enabled 

Trouble: BAT-Fire 

drops Phone 2 

line voltage

PGM4 Port 

Trouble Trigger

If using Point 

Capture 

(Figure 2)

Power Fail

Cover Tamper

Cell Fail

Ethernet Fail

CS Fail

CS Trouble

CS Fail

CS Fail**

Cover Tamper**

CS Fail

Figure 2:

BAT-Fire PGM4 

Output

(Any Enabled 

Trouble)

connected to

FACP/burg panel 

Trouble Input

   *   If Remote Programming is disabled, updates to site-specific parameters and BAT-Fire firmware are only permitted when the Config 

button on the BAT-Fire is pressed for 2 seconds.

 **   These trouble triggers are required to meet the UL864 and UL1610 standards. However, all other trouble triggers listed in the Possible 

Settings column are permitted. 

•  If Commercial Burg is selected, the more restrictive of the Fire and Burg timings will be used. 

•  ULC-S304 and ULC-S559 require 128 bit encryption or better. For active communications, the encryption shall be enabled at all times.

Содержание BAT-Fire AT&T

Страница 1: ...T Fire s DACT phone interface connection provides phone line voltage dial tone ringback tone and all required CID protocol signaling The BAT Fire receives CID events from the FACP burg panel s DACT and then relays the CID events to the central station receiver Point capture The BAT Fire provides inputs that can be used to monitor an FACP s alarm AC fail and trouble points dry contact outputs In th...

Страница 2: ...ation is complete 9 Press the Config button on the BAT Fire for 2 seconds to enable programming Program the BAT Fire via AlulaConnect see Programming section 10 Close the cover Confirm POWER TROUBLE and COMM LEDS are green 11 After installing BAT Fire or modifying any FACP burg panel programming verify proper operation and reporting of all event codes using your FACP burg panel installation manual...

Страница 3: ...ompany lines to the BAT Fire Attention ne connectez pas les lignes de votre compagnie téléphonique au BAT Fire It is recommended to use separate cables for Tip Ring 1 and Tip Ring 2 Failures and Troubles are communicated to FACP burg panel via the BAT Fire dropping voltage to Phone 2 Refer to Programming section on how to configure Phone 2 trouble triggers Stranded wire gauge range 24 14AWG If FAC...

Страница 4: ...2 by Honeywell relay The panel must support the relay contacts as indicated above NC for alarm and AC FAIL and NO for Trouble and battery calculation shall consider the additional current draw into the PGM s during the Normal Standby state Use 4 7k ohm 1 4 Watt minimum resistors not included PGM ports are not supervised Only panels without supervisory signaling can use this setup For UL 864 10th e...

Страница 5: ... not operational CS Fail Signal transmission to the central station is not operational Trouble Conditions The following trouble conditions can be communicated by BAT Fire to the FACP burg panel For UL 1610 installations refer to Programming section on how to configure BAT Fire s PGM3 as a ringback trigger A UL approved siren such as Honeywell Model 747 must be used for ringback The ringback featur...

Страница 6: ...tual interface supervision for both primary and backup Ethernet Remote Programming On site or Remote Enabled or Disabled Disabled Disabled Enabled or Disabled If Disabled Installer must press Config button onsite Phone 2 Trouble Trigger If using Phone Line capture Figure 1 Power Fail Cover Tamper Cell Fail Ethernet Fail CS Fail CS Trouble CS Fail CS Fail Cover Tamper CS Fail Figure 1 Any Enabled T...

Страница 7: ... and backup cellular Sole Path Cell 60 seconds 6 hours 1 hour 180 seconds or shorter 180 seconds or shorter Turn off Ethernet supervision Turn off virtual interface supervision for both primary and backup Ethernet Remote Programming On site or Remote Enabled or Disabled Disabled Enabled or Disabled Enabled or Disabled If Disabled Installer must press Config button onsite Phone 2 Trouble Trigger If...

Страница 8: ...sired output port Select Configure as Output Name output as desired Check all desired trouble triggers Power Fail Cover Tamper Cell Fail Ethernet Fail Central Station Fail Central Station Trouble Select Save Programming BAT Fire central station receiver s Select primary and backup optional receivers Adjust Supervision Interval based on wiring mode 6 hours default complies with UL 864 10th edition ...

Страница 9: ...ware is up to date Device Unused Cellular signal bar LEDs indicate the quality of the cellular connection A minimum of two signal bar LEDs is recommended Number of Signal Bar LEDs Lit Cellular Signal Strength 0 Bad 1 Marginal 2 Acceptable 3 Good 4 Best Operation and Indicator Overview Events are reported to the central station receivers and the Alula platform event system All events use Contact ID...

Страница 10: ... connected 2 Ensure router is powered 3 Ensure UDP ports 1234 and 1235 are open in router modem settings 4 Ensure account is properly configured Cellular LED Off 1 Verify sufficient signal strength for cellular see cellular signal bar table in Operation and Indicator Overview section 2 Ensure account is properly configured Comms LED Yellow 1 Verify the reporting path and ensure the receiver is pro...

Страница 11: ...Collector An output that when engaged shunts current to ground Point A single FACP burg panel output that is either on or off Point Capture The operation mode of BAT Fire connected to the FACP burg panel output s and sensing a trouble or alarm condition Additionally the operation of the FACP burg panel connected to a BAT Fire output and sensing a trouble or communication condition PSTN Public Swit...

Страница 12: ...020BG95M1 This Class B digital apparatus complies with Canadian ICES 003 Cet appareil numérique de la classe B est conforme à la norme NMB 003 du Canada TRADEMARKS Alula BAT Fire and AlulaConnect are trademarks owned by Alula Holdings LLC AT T is a trademark of AT T Intellectual Property II L P Verizon is a trademark of Verizon Trademark Services LLC Taoglas is a trademark of Taoglas Group Holding...

Отзывы: