Chapter 5 Parameter Introductions
http://www.acdrive-china.com
155
Fig. 5-5-4 PLC start mode 1
◆
Continue to operate at the frequency when the ac drive stops
When the ac drive stops during PLC operation because of receiving STOP command
or fault, it will record the operating time and the current frequency. It will continue
running at the recorded frequency after restart, as shown in Fig. 5-5-5.
T1
T2
T4
T5
Run command
f1
f2
f3
f4
f5
Operation Freq. (Hz)
Time
Stopping signal
Continue to operate at the frequency when the inverter stops
a1
a2
a3
a4
a5
Remnant time of stage 3
d3
Operating time of stage 3
Fig. 5-5-5 PLC start mode 2
Tips:
The difference between mode 1 and mode 2 is that the ac drive can record the operating
frequency when the ac drive stops and will run at the recorded frequency after restart in
mode 2.
P5.02 Saving PLC status when power off
Range: 0
~
1
【
0
】
0: Not save
1: Save
Note:
◆
Not save
The ac drive does not save the PLC operating state when the power is off and restart
from the first stage after the power is on.
◆
Save
The ac drive will save the PLC operating parameters such as the PLC operating stage,
PLC operating frequency, and PLC operating time when power is off. The ac drive
will continue the PLC operation from the status of power off after the power is on.
P5.03 Unit of step time
Range: 0
~
1
【
0
】
0: Second
1: Minute
Note:
◆
This unit is only valid for defining the PLC operating time. The unit of Acc/Dec time
in PLC operation is still second.