Chapter 5 Parameter Introductions
http://www.acdrive-china.com
119
P1.03 and P1.04 are only active when P1.00 is set to 1 (start mode 1 is selected), as
shown in Fig. 5-1-1.
The range of DC injection braking current and time are dependent on the ac drive model,
see Table 5-1-1.
DC injection braking current is a percentage value of ac drive rated current. When the
braking time is set to 0.0s, the DC injection braking process will not happen
Table 5-1-1 DC Injection braking function
Model
The range of current
The range of time
G
0.0
~
100.0%
0.0
~
30.0s
P
0.0
~
80.0%
0.0
~
30.0s
Note:
Refer to Fig. 5-1-1, the ac drive outputs DC injection braking current at start (P1.03),
during DC injection braking time at start.
Tips:
If the range of rated current of motor is smaller than the ac drive, this parameter value is
suggested to set as:
Motor rated current (A) / Ac drive rated current (A) * 100%
P1.05 Acc/Dec mode
Range: 0
~
3
【
0
】
0: Linearity
1:S-curve
2: Reserved
3: Reserved
Note:
◆
Linear Acc/Dec mode used for ordinary load: The output frequency increases or
decreases according to a constant rate. As shown in Fig. 5-1-4.
Output frequency(Hz)
Time
Preset Freq.
Acc time
Dec time
Fig. 5-1-4 Linear acceleration/deceleration
◆
Scurve change output frequency slowly at start of acceleration or end of deceleration,
in order to reduce mechanism noise and shake, lash of start and stop. It is suitable for
Содержание ALPHA6000 Series