Current transformer clipping
Clipping the current transformers onto the service
side cable:
1. Match the labelled CTs with their corresponding
labelled service supply cable.
2. Confirm correct polarity of the CT by ensuring
the arrow on the CT head matches the current
flow direction on the service supply cable.
3. Clip CT over service supply cable.
Important:
Make sure that each CT is clipped
to the corresponding unit.
Important:
The CT must be connected on the service
side of the point of connection of solar
supply, as per diagram.
POLARITY
OF CURRENT
TRANSFORMERS
DOWN TOWARDS
LOAD
R1
R1
FROM
SOLAR
SERVICE SIDE
LOAD SIDE
*
* The point of connection of the solar may appear
different in your case depending on the Project SLD.
In any case, the CT must be on the line side of the point
of connection of the solar supply.
C. Labeling
The SolShare comes with a Label Pack for you to use
where appropriate. Other labelling will also be required
based on your installation and local requirements. For
more information, refer to the SolShare Labelling Advice
document. Please refer below for information about
SolShare-specific labelling.
Leave a copy of the Project SLD at site to provide guidance
to any other electrician working on the switchboard.
X X X X X X
M1
X X X X X X
M2
X X X X X X
M3
X X X X X X
M4
6
5
4
3
2
1
7 8 9 10 11 12 13 14 15
X X X X X X
M5
X X X X X X
M6
X X X X X X
M7
X X X X X X
M8
X X X X X X
M9
X X X X X X
M10
X X X X X X
M11
X X X X X X
M12
X X X X X X
M13
X X X X X X
M14
X X X X X X
M15
WARNING
S
olar wired on the line/service side
of Tenancy Main Switches
F
ollow Solar Shutdown Procedure,
located on inverter(s), before
working on meter panel
Warning
Shared Solar System
To isolate a single unit:
1. Turn off their MAIN SWITCH INVERTER SUPPLY
2. Turn off their MAIN SWITCH NORMAL SUPPLY
X X X X X X
M1
X X X X X X
M2
X X X X X X
M3
X X X X X X
M4
6
5
4
3
2
1
7 8 9 10 11 12 13 14 15
X X X X X X
M5
X X X X X X
M6
X X X X X X
M7
X X X X X X
M8
X X X X X X
M9
X X X X X X
M10
X X X X X X
M11
X X X X X X
M12
X X X X X X
M13
X X X X X X
M14
X X X X X X
M15
WARNING
S
olar wired on the line/service side
of Tenancy Main Switches
F
ollow Solar Shutdown Procedure,
located on inverter(s), before
working on meter panel
Warning
Shared Solar System
To isolate a single unit:
1. Turn off their MAIN SWITCH INVERTER SUPPLY
2. Turn off their MAIN SWITCH NORMAL SUPPLY
Area of focus:
Labeling
Line side wiring
WARNING
Solar wired on the line/service side
of Tenancy Main Switches
Follow Solar Shutdown Procedure,
located on inverter(s), before
working on meter panel
NOTE: This must be visible from all meters (contact
Allume if additional labels are required). Do not apply this
label if SolShare connections have been made on the load
side of the Main Switch (Normal Supply). Instead, use a
standard multiple supplies warning label)).
Warning tenancy shutdown
Warning
Shared Solar System
To isolate a single unit:
1. Turn off their MAIN SWITCH INVERTER SUPPLY
2. Turn off their MAIN SWITCH NORMAL SUPPLY
NOTE: This must be visible from all Tenancy Main
Switches (contact Allume if additional labels are required).
Add these additional labels as suitable:
- SolShare Maintenance Isolator (Inverter) label
- SolShare Maintenance Isolator (Grid) labels
- Tenancy Main Switch (Inverter Supply) labels
- Tenancy Main Swtich (Normal Supply) labels
(not provided with SolShare)
South Australia only:
- Multiple supplies label next to each meter
- SolShare Inverter Supplies tags