18
A. Preparing the SolShare
Important:
- Before commissioning, re-check all CTs and output cables are connected as per their labels.
- Record connection information on commissioning notes page, you will need to enter this
while commissioning the unit after the cover is closed.
To power on the SolShare:
1. Pull down cover of SolShare. Fasten shut by replacing the 4 screws on the underside of the SolShare, that were
removed in section III/A.1. Maximum torque for cover fasteners is 1.5Nm
2. Turn on Inverter AC Isolator located next to inverter
3. Turn on Inverter Supply Main Switch
4. Ensure Main Switches (Normal Supply) are on
5. Turn on Main Switches (Inverter Supply)
To connect the SolShare to Wi-Fi (must be done within 5 mins of powering on the SolShare):
1. Using a laptop or phone (your device), connect your device to the SolShare SSID (this will appear as
SolShare3P_35A_XXXX where XXXX is the last 4 digits of the SolShare serial number).
2. Open an internet browser on your device and navigate to 192.168.4.1.
3. Once the page loads in the browser, enter the SSID and password of the Wifi network that you want the
SolShare to connect to.
4. Once you see a confirmation page in the browser, wait for the SolShare to reboot.
5. Disconnect your device from the SolShare SSID and reconnect it to the internet in preparation for the
commissioning steps below.
If you are having troubles with this process or need more detail, consult the How to set-up/change Wi-Fi credentials
document.
B. Commissioning the SolShare
1. To commission the SolShare, scan the QR
code on the right side of the SolShare or go to
https://commissioning.allumeenergy.com.au to
access the SolShare Commissioning App.
2. Follow the steps in the Commissioning App to
commission each SolShare. The Commissioning
App Guide provides more information on the
commissioning process.
NOTE: The SolShare requires a fully operational
inverter in order to complete commissioning. During
the SolShare commissioning process, you will be
prompted to commission the inverter. Please make
sure that the inverter is ready to be commissioned
prior to starting the commissioning process for the
SolShare.
3. If you experience issues with the commissioning
process contact Allume Service on +61 3 7038 0686
IV/ Commissioning