13
SolShare underside view
Each output membrane gland will correspond to the output of 3 single-phase units or 1 three-phase unit.
The leftmost membrane gland corresponds to the solar input.
Vent: do
not remove
input
solar
output
R1, W1, B1
output
R2, W2, B2
output
R3, W3, B3
output
R4, W4, B4
CT
conduit
gland
output
R5, W5, B5
Cover
retainer
screws
Area of input / output:
The 4c+e cables should be inserted
through the appropriate glands, as
per the ‘
SolShare underside view’
diagram above.
Warning:
The SolShare may divert all
solar energy to any one unit
in a point in time. As a result,
all input / output cables
should be sized for maximum
solar energy output.
The AC cables
Please choose appropriately
gauged cables as per solar
system size. The use of
four core and earth (4c+e)
is recommended. All input
and output cables should
be rated to total generation
capacity of inverter.
Warning: Outdoor Use requirements
Outdoor installation requires use of minimum
IP56 rated liquid tight cable or conduit gland
suitable for panel hole dimensions below.
Panel thickness: 4mm | Hole diameter: 32mm
Replace fitted membrane glands in base
panel with conduit fitting