Above ground splices may be used providing the wire is twisted, 
soldered and moisture sealed.  For best long  term results, do not use 
wire nuts anywhere in the loop system.  Connect  to the Vehicle 
Detector harness by soldering. 
 
For saw-cut  installations, observe the methods recommended in 
Figure 7, above.  The saw-cut must be to a depth of 1.5", clean and 
with no sharp corners.  After placing the wires, it is essential that the 
wires be held tightly in place by a foam backing prior to pouring the 
sealant.  THIS IS ESPECIALLY IMPORTANT WHEN FREEZING 
IS LIKELY.  No voids should exist that will permit the collection of 
water that might freeze and push the loop wires out of the slot.  The 
sealant used should not be hard setting and should be suitable for 
pavement  material. 

 

THE WIRE USED FOR THE LOOPS MUST BE HEAT AND 
WATER RESISTANT, CROSS-LINK POLYETHYLENE 
INSULATED.  TYPE XLPE IS BEST.  RHW IS O.K.  DO NOT 
USE ANY PVC INSULATED WIRE. (PVC insulation will absorb 
moisture that may affect Detector operation.)  WIRE SIZE SHOULD 
BE #16 GA. STRANDED OR LARGER.  

 

VEHICLE DETECTOR LOOP BLANKING FOR 
SWING GATES

 

 

The inside loop for a swing gate installation must be located at least 
4 feet outside of the arc of the gate.  If it is not, the Vehicle Detector 
may detect the gate as it moves over the loop and cause the Gate to 
reopen.  If the gate is large and a single leaf, the arc usually requires 
that the loop be a considerable distance from the closed gate position.  
This may not be an effective position for the loop.  In this case, a 
“blanking” or “shadow” loop may be used. 
When a Shadow Loop is necessary,  connect the output of the loop 
detector to terminal #9 “Shadow Loop” and terminal #16 
“Common”.  The GS4000 circuitry will recognize a vehicle on the 
loop and  prevent the gate from closing while the vehicle is over the 
Shadow Loop.  When the gate is closing or opening, the GS4000 
circuitry will ignore input from this loop as the gate swings over it. 
 
 
 

 
 
 

Figure 7:  Loop Diagrams 

104945 

B:

 PREPARING THE SITE 

Содержание ANSI/UL 325

Страница 1: ...for Vehicular gate operators GATE STAR 4000 Model GS4000 Heavy Duty Commercial Vehicular Swing Gate Operator READ THIS MANUAL CAREFULLY BEFORE INSTALLATION OR USE SAVE THESE INSTRUCTIONS 104950 Seria...

Страница 2: ...ere to protect you and your equipment Pay close attention to these boxes as you follow the manual WARNING Indicates a MECHANICAL hazard of INJURY OR DEATH Gives instructions to avoid the hazard CAUTIO...

Страница 3: ...cal parts Whether the overload is activated before the Torque Limiter slips will depend upon the tightness of the adjustment of the Torque Limiter This adjustment will be explained in the final check...

Страница 4: ...re a handhold or toehold may be achieved injuries may occur when people put arms through the openings or children ride the gate by standing on the bars and holding on to the gate THIS POTENTIAL HAZARD...

Страница 5: ...the GS4000 Control Box cover is removed high voltage will be exposed EVEN IF THE RED POWER LIGHT IS NOT LIGHTED HIGH VOLTAGE AC MAY STILL BE PRESENT ON TERMINALS L1 AND L2 NEVER LEAVE THE INSTALLATIO...

Страница 6: ...r attention to the bolt pattern and the location of the mounting holes with respect to the center line of the gate post It is critical for the proper operation of the Arm that the center line of the s...

Страница 7: ...O K DO NOT USE ANY PVC INSULATED WIRE PVC insulation will absorb moisture that may affect Detector operation WIRE SIZE SHOULD BE 16 GA STRANDED OR LARGER VEHICLE DETECTOR LOOP BLANKING FOR SWING GATES...

Страница 8: ...lt Amperes Watts IF TWO MECHANICAL UNITS ARE TO BE USED FOR A BI PARTING GATE SYSTEM THEN A 1000 VOLT AMPERE WATT TRANSFORMER MUST BE USED Operating from a three 3 phase line will require the use of a...

Страница 9: ...or connecting accessory equipment to the control box terminal strip and for limit switch control wires 7 Four 1 2 diameter concrete redhead bolts with hex nuts flat washers and lock washers For attach...

Страница 10: ...n accordance with the drawing of Figure 6 INSTALLING THE GS4000 ARM Temporarily locate the Gate Bracket on the Gate with C clamps or by tack welding Install the gate bracket to the gate so the gate ar...

Страница 11: ...t entry Run a flexible water tight conduit from the service junction box to the GS4000 CONTROL BOX Pull three 14 wires from the service junction box in this conduit to the GS4000 Control Box If the GS...

Страница 12: ...eriod of time is long enough to damage solid state components and many times other components The key to success is a very low resistance path from the surge protector to ground for these currents in...

Страница 13: ...tion one operator must be a Left Hand unit and the other a Right Hand unit The two motors of the Bi Parting GS4000 s will be wired in parallel BOTH motors will run until both are shut off If the two g...

Страница 14: ...14 C INSTALLING THE OPERATOR Figure 15 Bi Parting Installation Limit Motor Wiring Diagram 110092...

Страница 15: ...sary as the GS4000 control board 24 VAC output is not referenced to ground See Figure 16 and the following text for proper connection FOUR WIRE RECEIVERS Four wire receivers replace the spade terminal...

Страница 16: ...from a location where it will be switched off at the GS4000 Power Switch CONNECTING THE VEHICLE DETECTOR For a REVERSING LOOP connection of the Vehicle Detector the relay or presence output of the Det...

Страница 17: ...ME DESCRIPTION 1 24 VAC Provides maximum 10 VA auxiliary power for accessories 2 24 VAC Provides maximum 10 VA auxiliary power for accessories 3 ALTERNATE Momentary input must be released and re enter...

Страница 18: ...continuous signal This input is active only when referenced to the opening direction it has no effect on the gate when closing or about to close If activated when the gate is opening the gate will st...

Страница 19: ...operation as described in the text that follows OPEN CLOSE PUSH BUTTON ENABLE DISABLE PATENT NO 6 611 205 Switch S1 controls the Push Button Enable Disable Feature SWITCH 1 OFF Activating the Open or...

Страница 20: ...the application of power 1 Check that the GS4000 power switch is off 2 Check that the breaker at the power panel is on 3 With a voltmeter on the proper scale check that the line voltage at terminals...

Страница 21: ...tact Sensor light comes on remains on until the connection is removed Observe that the both Motor Open and Motor Close lights are momentarily ON then the Motor Open light goes out and the Motor Close...

Страница 22: ...ment run the GS4000 open and closed several times to ensure that the positions set will be retained SMART SETTING MAXIMUM RUN TIMER The GS4000 is equipped with a Self adjusting MAximum Run Timer SMART...

Страница 23: ...LM IN BOTH DIRECTIONS OF TRAVEL REPEAT THIS TEST UNTIL YOU ARE SATISFIED YOU HAVE THE MOST SENSITIVE SETTING OF THE POTENTIOMETERS Disconnect the crank arm from the output shaft to permit re installat...

Страница 24: ...signs shipped with your GS4000 Operator See Figure 4 Page 5 of this manual must be installed in prominent positions on both sides of your gate Keep them clean and legible Read and put into practice th...

Страница 25: ...ontact sensors After adjusting the force or limits of travel retest the gate operator Failure to adjust and retest the gate operator properly can increase the risk of injury or death KNOW YOUR GATE AR...

Страница 26: ...26 1 2 3 4 5 7 6 8 9 10 11 12 13 14 15 16 17 18 19 20 106359 Figure 27 GS4000 Mechanical Unit Exploded View MECHANICAL UNIT EXPLODED VIEW...

Страница 27: ...HANDY BOX 1 7 8 DEEP 19 102735 HANDY BOX COVER WITH LABEL SCREWS 20 010231 CLUTCH DISC ITEM PART DESCRIPTION 1 109966 CONTROL BOX W COVER 2 110074 CONTROL BOARD 3 100997 CIRCUIT BREAKER 4 010412 ON O...

Страница 28: ...labor charges for dismantling or reinstalling a repaired or replaced unit or replacement batteries These warranties are in lieu of all other warranties either expressed or implied All implied warranti...

Отзывы: