EXIT) and the RELAY COMMON signal connected to Terminal #16 
(COMMON) of the GS4000, See Figure 19. DO NOT CONNECT 
THE FREE EXIT OUTPUT SIGNAL TO ANY OTHER 
TERMINAL, SUCH AS RADIO OPEN, BECAUSE THE GATE 
WILL CLOSE AFTER REACHING THE OPEN LIMIT AND THE 
TIMER TO CLOSE HAS COMPLETED ITS CYCLE, EVEN 
THOUGH THE VEHICLE HAS NOT EXITED THE FREE OUT 
LOOP.

 

 
  

CONNECTING THE LOOP WIRES 

 

Follow the instructions of the Vehicle Detector Manufacturer when 
connecting the loop wires.  Good, tight connections are most 
important.  It is recommended that these wires be soldered to the 
wiring harness of the Vehicle Detector.

 

 
 
 
 
 

 
 

 
PRESETTING THE MOTOR OVERLOAD 
SENSITIVITY POTENTIOMETERS

 

 

The GS4000 has independent adjustments  for Open and Close 
Overload Sensitivity.  The GS4000 is shipped from the Factory with 
the overload settings at their most sensitive setting.  During the initial 
check out phase, it will be necessary to adjust the sensitivity to 
prevent inherent overloads from gate friction and other gate 
anomalies.  See Figure 20.  Adjust the OPEN and CLOSE 
OVERLOAD potentiometers approximately 1/4 turn clockwise.   
 
Note! Turning the potentiometer clockwise decreases sensitivity.  
Turning the potentiometer counterclockwise increases sensitivity. 

 

WARNING:  THE OVERLOAD POTENTIOMETERS MUST 
BE SET MORE PRECISELY PRIOR TO COMPLETING THE 
GS4000 INSTALLATION

.  (See, FINAL SETTING OF THE 

MOTOR OVERLOAD SENSITIVITY) 

 

WARNING! 

IMPROPER WIRING COULD CAUSE 

ELECTROCUTION OR DAMAGE TO CIRCUITRY.  

FOLLOW LOCAL BUILDING AND ELECTRICAL 

CODES. 

#  NAME 

DESCRIPTION 

1  24 VAC 

Provides maximum 10 VA auxiliary 
power for accessories. 

2  24 VAC 

Provides maximum 10 VA auxiliary 
power for accessories. 

3  ALTERNATE 

Momentary input, must be released 
and re-entered to be recognized.  

 

This input is used for “COMMAND OPEN/COMMAND 
CLOSE” applications.  The 1st signal will cause the gate 
to begin opening.  A 2nd signal received during the open 
cycle will stop the gate immediately.  A 3rd signal will 
close the gate.  Connect appropriate access control 
devices to this terminal and #16 COMMON.  Disable the 
Close Timer (rotate pot fully counter-clockwise).  

4  RADIO OPEN 

Momentary input, must be released 
and re-entered to be recognized.  

 

Once activated the gate will open fully.  Activation while 
the gate is closing will cause it to re-open.   

5  FREE EXIT 

Momentary or continuous input. 

 

 

Once activated the gate will open fully.  Activation while 
the gate is closing will cause it to re-open.  Continuous 
activation while the gate is open will prevent the Timer-
To-Close function from automatically closing the gate. 

 

6  OPEN 

Momentary or continuous signal. On/
Off mode set by Switch #1

 

 

WITH SWITCH 1 OFF:

 Once activated the gate will open 

fully.  Activation while the gate is closing will cause it to 
re-open.  Continuous activation while the gate is open 
will prevent the Timer-To-Close function from 
automatically closing the gate. Continuous signal 
required to move the gate when in the alarm mode. 

WITH SWITCH 1 ON:

 Gate does not respond to 

pushbutton input when in the normal mode. Continuous 
signal required to move the gate when in the alarm 
mode.  

 

TERMINAL STRIP REFERENCE CHART 

C: 

INSTALLING THE OPERATOR 

LOCATION OF 

ADJUSTMENTS

OVERLOAD FORCE

Figure 20:  Overload Force Adjustments 

110125 

Содержание ANSI/UL 325

Страница 1: ...for Vehicular gate operators GATE STAR 4000 Model GS4000 Heavy Duty Commercial Vehicular Swing Gate Operator READ THIS MANUAL CAREFULLY BEFORE INSTALLATION OR USE SAVE THESE INSTRUCTIONS 104950 Seria...

Страница 2: ...ere to protect you and your equipment Pay close attention to these boxes as you follow the manual WARNING Indicates a MECHANICAL hazard of INJURY OR DEATH Gives instructions to avoid the hazard CAUTIO...

Страница 3: ...cal parts Whether the overload is activated before the Torque Limiter slips will depend upon the tightness of the adjustment of the Torque Limiter This adjustment will be explained in the final check...

Страница 4: ...re a handhold or toehold may be achieved injuries may occur when people put arms through the openings or children ride the gate by standing on the bars and holding on to the gate THIS POTENTIAL HAZARD...

Страница 5: ...the GS4000 Control Box cover is removed high voltage will be exposed EVEN IF THE RED POWER LIGHT IS NOT LIGHTED HIGH VOLTAGE AC MAY STILL BE PRESENT ON TERMINALS L1 AND L2 NEVER LEAVE THE INSTALLATIO...

Страница 6: ...r attention to the bolt pattern and the location of the mounting holes with respect to the center line of the gate post It is critical for the proper operation of the Arm that the center line of the s...

Страница 7: ...O K DO NOT USE ANY PVC INSULATED WIRE PVC insulation will absorb moisture that may affect Detector operation WIRE SIZE SHOULD BE 16 GA STRANDED OR LARGER VEHICLE DETECTOR LOOP BLANKING FOR SWING GATES...

Страница 8: ...lt Amperes Watts IF TWO MECHANICAL UNITS ARE TO BE USED FOR A BI PARTING GATE SYSTEM THEN A 1000 VOLT AMPERE WATT TRANSFORMER MUST BE USED Operating from a three 3 phase line will require the use of a...

Страница 9: ...or connecting accessory equipment to the control box terminal strip and for limit switch control wires 7 Four 1 2 diameter concrete redhead bolts with hex nuts flat washers and lock washers For attach...

Страница 10: ...n accordance with the drawing of Figure 6 INSTALLING THE GS4000 ARM Temporarily locate the Gate Bracket on the Gate with C clamps or by tack welding Install the gate bracket to the gate so the gate ar...

Страница 11: ...t entry Run a flexible water tight conduit from the service junction box to the GS4000 CONTROL BOX Pull three 14 wires from the service junction box in this conduit to the GS4000 Control Box If the GS...

Страница 12: ...eriod of time is long enough to damage solid state components and many times other components The key to success is a very low resistance path from the surge protector to ground for these currents in...

Страница 13: ...tion one operator must be a Left Hand unit and the other a Right Hand unit The two motors of the Bi Parting GS4000 s will be wired in parallel BOTH motors will run until both are shut off If the two g...

Страница 14: ...14 C INSTALLING THE OPERATOR Figure 15 Bi Parting Installation Limit Motor Wiring Diagram 110092...

Страница 15: ...sary as the GS4000 control board 24 VAC output is not referenced to ground See Figure 16 and the following text for proper connection FOUR WIRE RECEIVERS Four wire receivers replace the spade terminal...

Страница 16: ...from a location where it will be switched off at the GS4000 Power Switch CONNECTING THE VEHICLE DETECTOR For a REVERSING LOOP connection of the Vehicle Detector the relay or presence output of the Det...

Страница 17: ...ME DESCRIPTION 1 24 VAC Provides maximum 10 VA auxiliary power for accessories 2 24 VAC Provides maximum 10 VA auxiliary power for accessories 3 ALTERNATE Momentary input must be released and re enter...

Страница 18: ...continuous signal This input is active only when referenced to the opening direction it has no effect on the gate when closing or about to close If activated when the gate is opening the gate will st...

Страница 19: ...operation as described in the text that follows OPEN CLOSE PUSH BUTTON ENABLE DISABLE PATENT NO 6 611 205 Switch S1 controls the Push Button Enable Disable Feature SWITCH 1 OFF Activating the Open or...

Страница 20: ...the application of power 1 Check that the GS4000 power switch is off 2 Check that the breaker at the power panel is on 3 With a voltmeter on the proper scale check that the line voltage at terminals...

Страница 21: ...tact Sensor light comes on remains on until the connection is removed Observe that the both Motor Open and Motor Close lights are momentarily ON then the Motor Open light goes out and the Motor Close...

Страница 22: ...ment run the GS4000 open and closed several times to ensure that the positions set will be retained SMART SETTING MAXIMUM RUN TIMER The GS4000 is equipped with a Self adjusting MAximum Run Timer SMART...

Страница 23: ...LM IN BOTH DIRECTIONS OF TRAVEL REPEAT THIS TEST UNTIL YOU ARE SATISFIED YOU HAVE THE MOST SENSITIVE SETTING OF THE POTENTIOMETERS Disconnect the crank arm from the output shaft to permit re installat...

Страница 24: ...signs shipped with your GS4000 Operator See Figure 4 Page 5 of this manual must be installed in prominent positions on both sides of your gate Keep them clean and legible Read and put into practice th...

Страница 25: ...ontact sensors After adjusting the force or limits of travel retest the gate operator Failure to adjust and retest the gate operator properly can increase the risk of injury or death KNOW YOUR GATE AR...

Страница 26: ...26 1 2 3 4 5 7 6 8 9 10 11 12 13 14 15 16 17 18 19 20 106359 Figure 27 GS4000 Mechanical Unit Exploded View MECHANICAL UNIT EXPLODED VIEW...

Страница 27: ...HANDY BOX 1 7 8 DEEP 19 102735 HANDY BOX COVER WITH LABEL SCREWS 20 010231 CLUTCH DISC ITEM PART DESCRIPTION 1 109966 CONTROL BOX W COVER 2 110074 CONTROL BOARD 3 100997 CIRCUIT BREAKER 4 010412 ON O...

Страница 28: ...labor charges for dismantling or reinstalling a repaired or replaced unit or replacement batteries These warranties are in lieu of all other warranties either expressed or implied All implied warranti...

Отзывы: