SETTING THE LIMIT SWITCHES

 

 
With the cover removed from the GS4000 MECHANICAL UNIT, 
and the arm connected to the gate as well as to the GS4000 Operator, 
position the gate at its 

FULLY CLOSED 

position.  Identify the 

lower Limit Switch.  Loosen the clamping nut on the Limit Switch 
Cam for the lower Limit Switch.   Rotate the cam on the output shaft 
until it engages the Limit Switch and an audible “click” is heard.  
Repeat this several times until you are confident that the position of 
the cam is such that the Limit Switch is just closed.  Carefully tighten 

the nut on the Limit Switch Cam.  Snug the set screw on the cam 
against the output shaft to protect the cam from accidental 
movement.  Open the gate to its 

FULLY OPEN

 position.  Repeat 

this procedure for the upper Limit Switch and Cam.  (See Figure 21.)   

 

SETTING THE SWITCH SELECTABLE OPTIONS

 

The switches that control the selectable options are located on the 
Control board.  See Figure 22. 
 

NO-LOAD TEST MODE 

 

To run/test the GS4000 operator when it is not connected to a gate 
leaf, turn all of the switches to the “ON” position.  The GS4000 can 
then be operated without a gate leaf attached for 20 complete cycles.  
If more that twenty cycles are attempted in the test mode the operator 
control board changes to a “sleep” mode and a low pulsed tone is 
heard from the audible output.  You can reset the operator for a 
renewed 20 test cycles by turning the power off and back on again.  
To return to normal operation turn one of the switches to the “OFF” 
position, then set all the switches to the desired mode of operation as 
described in the text that follows.

 

 

OPEN/CLOSE PUSH BUTTON ENABLE/
DISABLE (PATENT NO. 6,611,205) 

 

Switch S1 controls the Push Button Enable/Disable Feature. 

SWITCH 1 OFF:

 Activating the Open or Close buttons the gate will 

open or close fully.  Activation of the Open while the gate is closing 
will cause it to re-open.  Activation of the Close while the gate is 
opening has no effect.  Continuous activation of an opposing button 
while the gate is on a limit will prevent operation in that direction. 
Continuous signal required to move the gate when in the alarm mode. 

SWITCH 1 ON:

 Gate does not respond to pushbutton input when in 

the normal mode. Continuous signal required to move the gate when 
in the alarm mode.  This patented feature allows you to mount a two 
or three button station in an unsecured location as it will only be 
active when in the alarm mode. 

 

WARNING! 

RISK OF ELECTROCUTION 

DO NOT BEGIN TO SET THE FOLLOWING 

ADJUSTMENTS  UNTIL THE POWER IS TURNED 

OFF AT THE GS4000 CONTROL BOX 

D: 

STARTING THE OPERATOR 

#  NAME 

DESCRIPTION 

18  OPEN LIMIT 

SWITCH 

Connection for Limit Switch Input — See 
page 13, Fig. 13 or page 14, Fig. 15, for 
Limit Switch Wiring (single or bi-parting) 

M2  MOTOR RUN 

WINDING 

Connection for Motor wiring - See 
Section C.  Figs. 13 or 15 for Motor 
Wiring (single or bi-parting) 

M1  MOTOR RUN 

WINDING 

Connection for Motor wiring - See 
Section C.  Figs. 13 or 15 for Motor 
Wiring (single or bi-parting) 

L2  AC INPUT 

Also connection for MOTOR COMMON 

L1  AC INPUT 

 

UPPER LIMIT 
SWITCH 

LOWER  LIMIT 
SWITCH 

SET SCREW 

LOWER LIMIT 
CAM 

LOWER 
LIMIT CAM 
CLAMPING 
NUT 

UPPER 

LIMIT CAM 

CLAMPING 

NUT 

UPPER 

LIMIT 

CAM 

106304 

Figure 21: Limit Switches 

 TERMINAL STRIP REFERENCE CHART 

ABLE OPTIONS

SWITCH SELECT-

LOCATION OF 

110126 

Figure 22:  SETTABLE SWITCHES 

Содержание ANSI/UL 325

Страница 1: ...for Vehicular gate operators GATE STAR 4000 Model GS4000 Heavy Duty Commercial Vehicular Swing Gate Operator READ THIS MANUAL CAREFULLY BEFORE INSTALLATION OR USE SAVE THESE INSTRUCTIONS 104950 Seria...

Страница 2: ...ere to protect you and your equipment Pay close attention to these boxes as you follow the manual WARNING Indicates a MECHANICAL hazard of INJURY OR DEATH Gives instructions to avoid the hazard CAUTIO...

Страница 3: ...cal parts Whether the overload is activated before the Torque Limiter slips will depend upon the tightness of the adjustment of the Torque Limiter This adjustment will be explained in the final check...

Страница 4: ...re a handhold or toehold may be achieved injuries may occur when people put arms through the openings or children ride the gate by standing on the bars and holding on to the gate THIS POTENTIAL HAZARD...

Страница 5: ...the GS4000 Control Box cover is removed high voltage will be exposed EVEN IF THE RED POWER LIGHT IS NOT LIGHTED HIGH VOLTAGE AC MAY STILL BE PRESENT ON TERMINALS L1 AND L2 NEVER LEAVE THE INSTALLATIO...

Страница 6: ...r attention to the bolt pattern and the location of the mounting holes with respect to the center line of the gate post It is critical for the proper operation of the Arm that the center line of the s...

Страница 7: ...O K DO NOT USE ANY PVC INSULATED WIRE PVC insulation will absorb moisture that may affect Detector operation WIRE SIZE SHOULD BE 16 GA STRANDED OR LARGER VEHICLE DETECTOR LOOP BLANKING FOR SWING GATES...

Страница 8: ...lt Amperes Watts IF TWO MECHANICAL UNITS ARE TO BE USED FOR A BI PARTING GATE SYSTEM THEN A 1000 VOLT AMPERE WATT TRANSFORMER MUST BE USED Operating from a three 3 phase line will require the use of a...

Страница 9: ...or connecting accessory equipment to the control box terminal strip and for limit switch control wires 7 Four 1 2 diameter concrete redhead bolts with hex nuts flat washers and lock washers For attach...

Страница 10: ...n accordance with the drawing of Figure 6 INSTALLING THE GS4000 ARM Temporarily locate the Gate Bracket on the Gate with C clamps or by tack welding Install the gate bracket to the gate so the gate ar...

Страница 11: ...t entry Run a flexible water tight conduit from the service junction box to the GS4000 CONTROL BOX Pull three 14 wires from the service junction box in this conduit to the GS4000 Control Box If the GS...

Страница 12: ...eriod of time is long enough to damage solid state components and many times other components The key to success is a very low resistance path from the surge protector to ground for these currents in...

Страница 13: ...tion one operator must be a Left Hand unit and the other a Right Hand unit The two motors of the Bi Parting GS4000 s will be wired in parallel BOTH motors will run until both are shut off If the two g...

Страница 14: ...14 C INSTALLING THE OPERATOR Figure 15 Bi Parting Installation Limit Motor Wiring Diagram 110092...

Страница 15: ...sary as the GS4000 control board 24 VAC output is not referenced to ground See Figure 16 and the following text for proper connection FOUR WIRE RECEIVERS Four wire receivers replace the spade terminal...

Страница 16: ...from a location where it will be switched off at the GS4000 Power Switch CONNECTING THE VEHICLE DETECTOR For a REVERSING LOOP connection of the Vehicle Detector the relay or presence output of the Det...

Страница 17: ...ME DESCRIPTION 1 24 VAC Provides maximum 10 VA auxiliary power for accessories 2 24 VAC Provides maximum 10 VA auxiliary power for accessories 3 ALTERNATE Momentary input must be released and re enter...

Страница 18: ...continuous signal This input is active only when referenced to the opening direction it has no effect on the gate when closing or about to close If activated when the gate is opening the gate will st...

Страница 19: ...operation as described in the text that follows OPEN CLOSE PUSH BUTTON ENABLE DISABLE PATENT NO 6 611 205 Switch S1 controls the Push Button Enable Disable Feature SWITCH 1 OFF Activating the Open or...

Страница 20: ...the application of power 1 Check that the GS4000 power switch is off 2 Check that the breaker at the power panel is on 3 With a voltmeter on the proper scale check that the line voltage at terminals...

Страница 21: ...tact Sensor light comes on remains on until the connection is removed Observe that the both Motor Open and Motor Close lights are momentarily ON then the Motor Open light goes out and the Motor Close...

Страница 22: ...ment run the GS4000 open and closed several times to ensure that the positions set will be retained SMART SETTING MAXIMUM RUN TIMER The GS4000 is equipped with a Self adjusting MAximum Run Timer SMART...

Страница 23: ...LM IN BOTH DIRECTIONS OF TRAVEL REPEAT THIS TEST UNTIL YOU ARE SATISFIED YOU HAVE THE MOST SENSITIVE SETTING OF THE POTENTIOMETERS Disconnect the crank arm from the output shaft to permit re installat...

Страница 24: ...signs shipped with your GS4000 Operator See Figure 4 Page 5 of this manual must be installed in prominent positions on both sides of your gate Keep them clean and legible Read and put into practice th...

Страница 25: ...ontact sensors After adjusting the force or limits of travel retest the gate operator Failure to adjust and retest the gate operator properly can increase the risk of injury or death KNOW YOUR GATE AR...

Страница 26: ...26 1 2 3 4 5 7 6 8 9 10 11 12 13 14 15 16 17 18 19 20 106359 Figure 27 GS4000 Mechanical Unit Exploded View MECHANICAL UNIT EXPLODED VIEW...

Страница 27: ...HANDY BOX 1 7 8 DEEP 19 102735 HANDY BOX COVER WITH LABEL SCREWS 20 010231 CLUTCH DISC ITEM PART DESCRIPTION 1 109966 CONTROL BOX W COVER 2 110074 CONTROL BOARD 3 100997 CIRCUIT BREAKER 4 010412 ON O...

Страница 28: ...labor charges for dismantling or reinstalling a repaired or replaced unit or replacement batteries These warranties are in lieu of all other warranties either expressed or implied All implied warranti...

Отзывы: