Preface
MicroLogix 1000 Programmable Controllers User Manual
2–22
Wiring Your Analog Channels
Analog input circuits can monitor current and voltage signals and convert
them to serial digital data. The analog output can support either a voltage or
a current function.
VAC
VDC
O/4
O/5
O/6
NOT
USED
O/7
I/10
I/11
IA
(–)
IA/3
I (+)
IA/2
I (+)
IA
SHD
IA/1
V (+)
IA
SHD
IA/0
V (+)
IA
(–)
OA
(–)
OA/0
I (+)
OA/0
V (+)
OA
SHD
– OR –
Jumper
unused
inputs.
Sensor 1
Sensor 2
Sensor 3
Sensor 4
meter
(V) Voltage
(V) Voltage
(I) Current
(I) Current
You can configure either voltage
or current output operation.
For increased noise immunity, connect a ground wire directly from the
shield terminals to chassis ground.
2-Wire Transmitter
Transmitter
+
–
4-Wire Transmitter
Transmitter
Supply
Signal
+
–
+
–
IA/0 – 3 (+)
IA (–)
Controller
IA/0 – 3 (+)
IA (–)
Controller
+
Power
Supply
–
+
Power
Supply
–
Important: The controller does not provide loop power for analog inputs.
Use a power supply that matches the transmitter specifications.