Preface
MicroLogix 1000 Programmable Controllers User Manual
9–12
Using FLL
The following figure shows how file instruction data is manipulated. The
instruction fills the words of a file with a source value. It uses no status bits. If you
need an enable bit, program a parallel output that uses a storage address.
Source
Destination
Word to File
Entering Parameters
Enter the following parameters when programming this instruction:
•
Source is a constant or element address. The file indicator (#) is not required
for an element address.
•
Destination is the starting address of the file you want to fill. You must use the
file indicator (#) in the address.
•
Length is the number of words or elements in the file to be filled.
f
e des na on f le ype s a:
then you can specify a maximum length of:
If the destination file type is a:
Discrete
Analog
Output
1
5
Input
2
8
Status
33
33
Bit
32
32
Timer
40
40
Counter
32
32
Control
16
16
Integer
105
105
All elements are filled from the source value (typically a constant) into the specified
destination file each scan the rung is true. Elements are filled in ascending order.