Preface
MicroLogix 1000 Programmable Controllers User Manual
A–6
Analog Input Specifications
Description
Specification
Voltage Input Range
–10.5 to +10.5V dc – 1LSB
Current Input Range
–21 to +21 mA – 1LSB
Type of Data
16-bit signed integer
Input Coding –21 to +21 mA – 1LSB, –10.5 to +10.5V dc –
1LSB
–32,768 to +32,767
Voltage Input Impedance
210K
W
Current Input Impedance
160
W
Input Resolution
➀
16 bit
Non-linearity
t
0.002%
Overall Accuracy 0
°
C to +55
°
C
±
0.7% of full scale
Overall Accuracy Drift 0
°
C to +55
°
C (max.)
±
0.176%
Overall Accuracy at +25
°
C (+77
°
F) (max.)
±
0.525%
Voltage Input Overvoltage Protection
24V dc
Current Input Overcurrent Protection
±
50 mA
Input to Output Isolation
0V
00V
60 H
Field Wiring to Logic Isolation
30V rated working/500V test 60 Hz/1s
➀
The analog input update rate and input resolution are a function of the input filter selection. For
additional information, see page 5–3.
Analog Output Specifications
Description
Specification
Voltage Output Range
0 to 10V dc –1LSB
Current Output Range
4 to 20 mA – 1LSB
Type of Data
16-bit signed integer
Non-linearity
0.02%
Step Response
2.5 ms (at 95%)
Load Range – Voltage Output
1K
W
to
1
W
Load Range – Current Output
0 to 500
W
Output Coding 4 to 20 mA – 1 LSB, 0 to 10Vdc – 1LSB
0 to 32,767
Voltage Output Miswiring
can withstand short circuit
Current Output Miswiring
can withstand short circuit
Output Resolution
15 bit
Analog Output Settling Time
3 msec (maximum)
Overall Accuracy 0
°
C to +55
°
C
±
1.0% of full scale
Overall Accuracy Drift 0
°
C to +55
°
C (max.)
±
0.28%
Overall Accuracy at +25
°
C (+77
°
F) (max.) – Current Output
0.2%
Field Wiring to Logic Isolation
30V rated working/500V isolation