Publication 1756-UM522B-EN-P - February 2003
1756-DMF30 Specific Information C-107
Parameter 2123 [MC Warnings]
This parameter indicates the occurance of a motor-control warning
event. These bits are set when a warning event is detected. They
stay latched until bit 19 [Clear Fault] of parameter 152 [Applied Logic
Cmd] or bit 19 [Clr Drv Wrn] of parameter 166 [Motor Ctrl Cmd] is set.
If the warning event remains present, the identifying bit is set again.
Refer to parameter 381 [PMI Warning Cnfg] to configure the Drive
Module's response to these warnings.
12
PMI Pwr Sply
The PMI power supply is not working correctly.
13
PMI Bus
There is a bus fault in the PMI rack. This is indicated
when the Resolver and Drive l/O module and the DC
Power Technology module do not respond to requests
from the PMI Processor. This error indicates that
there is a hardware problem in the rack.
15
PMI CommLoss
Communication between the PMI processor and the
Drive Module has failed.
Bit
Fault Name
Fault Description
0
BrdgNotFirng
Not all SCRs are carrying the same the load. A bit set
in the parameter 2124 [Pwr DeviceStatus] indicates
which SCR is not working properly.
1
Low AC Line
AC line voltage is less than 85% of its nominal value,
which was entered as a configuration parameter. This
can be caused by a low-line condition or a missing
phase. The system will automatically adjust the
phase angle to give the correct current amount and
will continue to fire SCRs as long as zero crossings
are detected. If zero crossings are no longer detected,
a fault condition will result.
3
LineSyncLoss
The system is continuing to operate through a
temporary loss of AC line voltage. Refer to bit 3 [AC
Line Sync] of parameter 2122 [MC Fault].
4
Curr Ref Lim
The current reference has exceeded the value
entered in parameter 2184 [PMI Curr Lim].
5
ID TestAbort
The drive has failed an armature identification test,
field identification test or resolver balance
calibration test.
6
Fld OvrCurr
Field current has exceeded 150% of the value in
parameter 2185 [Hot Field Curr].
7
3Ph Fdbk Rev
Three-phase feedback wiring is reversed - the
polarity of the feedback is the oposite of expected.
8
CT Fdbk Rev
Current transformer feedback is reversed - the
polarity of the feedback is the oposite of expected.
Bit
Fault Name
Fault Description
Содержание ControlLogix 1756-DMD30
Страница 1: ...ControlLogix Drive Module 1756 DMD30 1756 DMF30 User Manual y...
Страница 4: ......
Страница 8: ...Publication 1756 UM522B EN P February 2003 4...
Страница 10: ...Publication 1756 UM522B EN P February 2003 Summary of Changes 2 Notes...
Страница 14: ...Publication 1756 UM522B EN P February 2003 Preface 4 Notes...
Страница 26: ...Publication 1756 UM522B EN P February 2003 2 4 Drive Comm Drive Communication Notes...
Страница 44: ...Publication 1756 UM522B EN P February 2003 4 8 Installing the Drive Module Notes...
Страница 252: ...Publication 1756 UM522B EN P February 2003 B 172 1756 DMD30 Specific Information Notes...