Publication 1756-UM522B-EN-P - February 2003
B-76 1756-DMD30 Specific Information
381
PMI Warning Cnfg
Enter a value to configure the drive's response to a "PMI
Warning" exception event (events enumerated in parameter
2123 [MC Warnings].
•
Value 0 - Ignore configures the drive module to
continue running as normal, in response to this event
•
Value 1 - Alarm configures the drive module to set the
appropriate alarm bit in response to this event
•
Value 2 - FltCoastStop configures the drive module to
perform a coast stop and set the appropriate fault bit in
response to this event
•
Value 3 - FltRampStop configures the drive module to
perform a ramp stop and set the appropriate fault bit in
response to this event
•
Value 4 - CurLimStp configures the drive module to
perform a current limit stop and set the appropriate
fault bit in response to this event
Default
Val 1
Alarm
Options:
Val 0
Val 1
Val 2
Val 3
Val 4
Ignore
Alarm
FltCoastStop
FltRampStop
FltCurLimStp
File:
Group:
Utility
Fault/Alm Config
382
Lgx OutOfRunCnfg
Enter a value to configure the drive's response to the
ControlLogix processor being in Non-Run mode. Non-Run
modes include Program, Remote-Program and Faulted.
•
Value 0 - Ignore configures the drive module to
continue running as normal, in response to this event
•
Value 1 - Alarm configures the drive module to set the
appropriate alarm bit in response to this event
•
Value 2 - FltCoastStop configures the drive module to
perform a coast stop and set the appropriate fault bit in
response to this event
•
Value 3 - FltRampStop configures the drive module to
perform a ramp stop and set the appropriate fault bit in
response to this event
•
Value 4 - CurLimStp configures the drive module to
perform a current limit stop and set the appropriate
fault bit in response to this event
Default
Val 2
FltCoastStop
Options:
Val 0
Val 1
Val 2
Val 3
Val 4
Ignore
Alarm
FltCoastStop
FltRampStop
FltCurLimStp
File:
Group:
Utility
Fault/Alm Config
No.
Name
Description
Values
ATTENTION
!
Risk of injury or equipment damage exists. Parameter 382 [Lgx
OutOfRunCnfg] lets you determine the action of the drive if communications
are disrupted. By default this parameter causes the drive to fault and coast to
a stop. You can set this parameter so that the drive continues to run.
Precautions should be taken to ensure that the setting of this parameter does
not create a hazard of injury or equipment damage.
Содержание ControlLogix 1756-DMD30
Страница 1: ...ControlLogix Drive Module 1756 DMD30 1756 DMF30 User Manual y...
Страница 4: ......
Страница 8: ...Publication 1756 UM522B EN P February 2003 4...
Страница 10: ...Publication 1756 UM522B EN P February 2003 Summary of Changes 2 Notes...
Страница 14: ...Publication 1756 UM522B EN P February 2003 Preface 4 Notes...
Страница 26: ...Publication 1756 UM522B EN P February 2003 2 4 Drive Comm Drive Communication Notes...
Страница 44: ...Publication 1756 UM522B EN P February 2003 4 8 Installing the Drive Module Notes...
Страница 252: ...Publication 1756 UM522B EN P February 2003 B 172 1756 DMD30 Specific Information Notes...