Publication 1756-UM522B-EN-P - February 2003
1756-DMF30 Specific Information C-89
2131
FML Feedback
Displays measured field current. A value of 4095 indicates hot
field current - equal to the value of parameter 2185 [Hot Field
Curr].
Units:
Default:
Min:
Max:
Type:
File:
Group:
P.U.
0
-4095
4095
Non-Linkable, Read-Only, 16-Bit Integer
DPS/PMI
Feedback
2132
Field Amps Fdbk
Displays measured field current in Amps x 10, (e.g., a value of
501 indicates 50.1A).
Units:
Default:
Min:
Max:
Type:
File:
Group:
Amps
0
-32768
32767
Non-Linkable, Read-Only, Floating Point
DPS/PMI
Feedback
2133
Field Volt Fdbk
Displays the field voltage feedback value, in volts. This voltage
is calculated based on the AC line voltage and field firing
angle.
Units:
Default:
Min:
Max:
Type:
File:
Group:
Volt
0
-32768
32767
Non-Linkable, Read-Only, Floating Point
DPS/PMI
Feedback
2134
User Anlg Input
Displays the measured user analog input value from the
Resolver Feedback connector on the Resolver & Drive l/O
module. This value may be accessed through the PMI meter
ports.
Default:
Min:
Max:
Type:
File:
Group:
0
-2048
2048
Non-Linkable, Read-Only, 16-Bit Integer
DPS/PMI
Feedback
2135
Res Scan Posit
Displays the electrical position of the resolver (if used). This
register is reset to zero at power-up.
Default:
Min:
Max:
Type:
File:
Group:
0
-32768
32767
Non-Linkable, Read-Only, 16-Bit Integer
Speed/Posit Fdbk, DPS/PMI
Resolver, Feedback
2136
Res Strobe Posit
Displays the electrical position of the resolver at the time a
strobe signal is detected.
Default:
Min:
Max:
Type:
File:
Group:
0
-32768
32767
Non-Linkable, Read-Only, 16-Bit Integer
DPS/PMI
Feedback
2149
NV Faults
Non Volatile storage location for internal module faults.
Rockwell development personnel may use the value in this
register to debug the module firmware.
Default:
Min:
Max:
Type:
File:
Group:
0
0
4294967296
Non-Linkable, Read-Only, 32-Bit Integer
DPS/PMI
Feedback
2150
CML Crossovr Frq
Enter a value to determine the response of the current minor
loop. Higher values improve response. However, higher
values may degrade stability.
Units:
Default:
Min:
Max:
Type:
File:
Group:
R/S
200
0
400
Linkable, Read-Write, 16-Bit Integer
DPS/PMI
Regulator Config
No.
Name
Description
Values
Содержание ControlLogix 1756-DMD30
Страница 1: ...ControlLogix Drive Module 1756 DMD30 1756 DMF30 User Manual y...
Страница 4: ......
Страница 8: ...Publication 1756 UM522B EN P February 2003 4...
Страница 10: ...Publication 1756 UM522B EN P February 2003 Summary of Changes 2 Notes...
Страница 14: ...Publication 1756 UM522B EN P February 2003 Preface 4 Notes...
Страница 26: ...Publication 1756 UM522B EN P February 2003 2 4 Drive Comm Drive Communication Notes...
Страница 44: ...Publication 1756 UM522B EN P February 2003 4 8 Installing the Drive Module Notes...
Страница 252: ...Publication 1756 UM522B EN P February 2003 B 172 1756 DMD30 Specific Information Notes...