130
Rockwell Automation Publication ICSTT-RM448J-EN-P - April 2018
Chapter 5
Install the AADvance System
Status Indicators on the 9110 Processor Module
Table 11 - Status Indicators on the T9110 Processor Module
Indicator
Status
Description
Healthy
OFF
No power.
RED
• Flashes RED briefly after being installed as the module is booting up
• Continuous RED means a Module has a fault.
GREEN
As the module boots up it goes GREEN, this lasts for 10 to 20 seconds.
When the module is operational the LED stays GREEN.
When in the recovery mode and no faults are present the LED is GREEN.
Fault Indications:
• If Healthy is GREEN and all the other indicators on the module are OFF then the
module has failed to boot up.
• If Healthy is GREEN and Ready and Run are RED then the module is in its
shutdown state.