Rockwell Automation Publication ICSTT-RM448J-EN-P - April 2018
99
Install the AADvance System
Chapter 5
Connect a Slave Device, Full Duplex
You can use a full duplex serial connection to connect one MODBUS Slave
device to the AADvance controller. To make the physical connection, do the
following:
1. Select an applicable cable. We recommend 3-pair, overall shielded cable.
2. Remove the serial port connector from the 9100 processor base unit.
3. Make the connections shown in the illustration. Terminate the twisted
pairs with a 120
resistor in series with a 68 nF capacitor at the receiver
ends.
4. Connect the signal ground (not illustrated) from the 0 V terminal to the
slave device.
5. Insert the connector into the 9100 processor base unit.
IMPORTANT
Do not connect the signal ground to the AC safety ground.