Rockwell Automation Publication ICSTT-RM448J-EN-P - April 2018
113
Install the AADvance System
Chapter 5
Connections to T9832/T9833 Isolated Analogue Input TA — 16 Channel TMR
• Apply a minimum tightening torque of 0.5 Nm (0.37 ft. lb.) to the
terminal screws.
Recommended Field Circuit for Digital Outputs
This circuit is applicable for simplex and dual configurations of digital output
modules. The two 10 A fuses shown are included on the termination assembly
within the controller. The 5 A fuses satisfy UL508 requirements for digital
output field supplies, see illustration below: