KM 255 en
General
V1.0
7
1.2.3
Accuracy
1.2.4
Admission Pressure and Counterpressure / Suction Height
Maximum admission pressure at the suction side [bar]
Minimum counterpressure at the pressure valve of the pump [bar]
Note
A positive pressure difference of 2 bar min. is required between the suction valve
and the pressure valve in order for the dosing pump to operate correctly. If the total
counterpressure (at the dosing point) and geodetic height difference between the
suction valve and the dosing point is less than 2 bar (20 m WS), a pressure
retention valve must be installed directly in front of the dosing point.
Maximum counterpressure* [bar]
*Observe the maximum permissible temperatures
Maximum suction height * [m] for media with a viscosity similar to water
*applies to a filled dosing head
Maximum suction height [m] for media with maximum permissible viscosity
1.2.5
Sound Pressure Level
1.2.6
Degree of Protection
Depending on the motor variant that is selected, see type plate of the motor.
The specified degree of protection can only be ensured, if the mains cable is connected
with the same degree of protection.
Dosing flow
fluctuation
smaller ± 1 %
Linearity
deviation
±1 % of the full-scale value (for water with a fully deaerated
dosing head)
Type
[bar]
KM 255
0,8
Type
[bar]
KM 255
2
Type
Singlepump
Doublepump
p max
[bar]
255-194
255-194/2
10
255-270
255-270/2
255-332
255-332/2
255-403
255-403/2
255-550
255-550/2
Type
Singlepump
Doublepump
Suction height
max. [m WS]
255-194
255-194/2
flooded suction
255-270
255-270/2
255-332
255-332/2
255-403
255-403/2
255-550
255-550/2
Type
[m]
KM 255
flooded suction
Type
KM 255
75 ± 5 dB (A), testing according to DIN 45635-01-KL3