16 

 

dispensing of pellets stops and the flue gas motor and ambient fan are operating at maximum capacity in order to cool the 
oven as soon as possible. Minimal duration of the shutting off phase is 30 seconds, and the condition for the furnace to 
cool down completely is for the temperature of flue gases to be less than 68°C. 

 

4.5.8

 

OFF

 

In this state, the furnace is turned off i.e. no output on the furnace (flue gas motor, ambience fan, lighter and auger) is 

active. 

 

4.5.9

 

Block

 

The blockage condition occurs in the event of error or alarm. In the block mode, the fan of the exhaust gases, auger and 

lighters are off. To exit, hold P2 pressed for 3 seconds: if it is no longer blocked and there is no cause for alarm, the system 
will shut down. 

 

4.5.10

 

Ignition Recover

 

The furnace moves to this phase in two cases: 

5

 

If a power failure occurs during the operating mode and the flue gas temperature is higher than 50°C. 

6

 

Pressing the main switch at the moment when the furnace is in the shutting down phase. 

 
 

 

Other functions 

4.6.1

 

Voltage shortage management

 

 In the event of power failure, the system keeps the most important functional data. With the return of the voltage, the 

system assesses the saved data and: 

 

If the furnace is turned on and the temperature of the exhaust gases is higher than 50°C, the system switches to 

the Ignition recovery. By pressing the P1 button, a sudden new ignition of the system is possible. 

 

If the furnace is on, but the temperature of exhaust gases is less than 50°C, the system enters shutdown with 

error Er15

 

If the furnace is switched off or during shutting off or while blocked, the system returns to its previous state. 

 

In the absence of voltage over a period of one week, the system becomes blocked with an error message Er11 

indicating that the DATE / TIME is not accurate. Deblock using the P1 button, the value of TIME flashes, signalling the need 
for updating the TIME and DATE with the function CLOCK.

 

 

4.6.2

 

Pellet feeding calibration management 

 

The user has the possibility to calibrate the dosing of pellets in the User menu 1.  Calibration range from -7 ÷ 7. 1=5%. 

Each calibration of the pellet dosing is applied percentually to all work powers. E.g. if set to -1 then the pellet dosing would 
decrease by 5% in all operating modes (Power 1 - 5). 

Example 

Before 

calibration 

Power 1 = 

2.0 

Power 2 = 

3.0 

Power 3 = 

4.0 

Power 4 = 

5.0 

Power 5 = 6.0 

Step = -1 

Power 1 = 

1.9 

Power 2 = 

2.85 

Power 3 = 

3.8 

Power 4 = 

4.75 

Power 5 = 5.7 

Never calibrate the pellet dosing without consultations with the repair shop. 

 

4.6.3

 

Managing the correction of the  flue gas motor

 

The user has the possibility to calibrate the speed of flue gases motor in the User menu 1. Calibration range from -7 ÷ 7. 

1=5%.  Each  calibration  is  applied  percentually  to  all  work  powers.  E.g.  if  set  to  3  then  the  flue  gas  motor  speed  would 
increase by 15% (3x5%) in all operating modes (Power 1 - 5). 

Exampl

Before 

calibration 

Power 1 = 

1000 

Power 2 = 

1200 

Power 3 = 

1400 

Power 4 = 

1600 

Power 5 = 1800 

 

Step = +3 

Power 1 = 

1150 

Power 2 = 

1380 

Power 3 = 

1610 

Power 4 = 

1840 

Power 4 = 2070 

Never calibrate the speed of flue gas motor without consultations with the repair shop. 

 

4.6.4

 

Safety thermostat

 

In case the temperature of the pellets in the tank reaches a value greater than 90°C, a safety thermostat is activated in 

order to prevent the ignition of the pellets in the tank. The system moves to the blockage mode of work and the alarm 
message Er01 appears. 

 

 

4.6.5

 

Periodical cleaning of the furnace

 

When the system is in stable condition, after a specified time interval (every 45 minutes), the system automatically 

performs periodic cleaning for 30 seconds. 

During the periodic cleaning, the flue gas motor works with increased intensity and the dosing of pellets stops. 

 

Содержание LUCA S

Страница 1: ...his user manual is an integral part of the product It has to be kept and read carefully METAL INDUSTRY VRANJE st Radni ka n 1 PELLET STOVE LUCA S LUCA S8 INSTRUCTIONS FOR ASSEMBLY USE AND MAINTENANCE...

Страница 2: ...ommissioning is performed by qualified personnel Do not use any flammable liquids for the ignition process This product should not be used by people with reduced physical sensory and mental abilities...

Страница 3: ...essary controls and checks for first ignition 9 3 2Fuel feed 9 4 Furnace management system 10 4 1Electric wiring scheme 10 4 2The control panel display use and functions 11 4 2 1 Display K100 11 4 2 2...

Страница 4: ...oblems and solutions 17 5 STOVE MAINTENANCE 18 5 1Routine maintenance 18 5 1 1 CLEANING OF THE DISPLAY AND PARTS OF THE EXTERNAL INSULATION 18 5 1 2 CLEANING OF THE CERAMIC GLASS 18 5 1 3 ROUTINE MAIN...

Страница 5: ...gher level and so as to improve the final product Seals which provide sealing of the combustion chamber must be periodically inspected to prevent undesirable combustion which may occur due to excessiv...

Страница 6: ...3 2 7 Emission of CO at 13 of oxygen 0 0136 0 0213 Efficiency 85 57 92 27 Rated electric energy W 380 Rated voltage V 230 Rated frequency Hz 50 Fuel Pellet Fuel consumption per hour kg h 1 608 0 642...

Страница 7: ...to 8 mm in the radius Wood pellets are primarily characterised by low humidity below 12 and high density 600 kg m3 as well as by its uniformity and compactness which gives this type of fuel high calor...

Страница 8: ...by the manufacturer may lead to failure of the furnace and may void the warranty When feeding the pellets be careful the pellet does not fall into another internal part of the furnace other than the s...

Страница 9: ...he product is equipped with the following safety devices Thermostat for determining the temperature of the tank This device shuts down operation of the product each time the set safety limit is exceed...

Страница 10: ...diminished 4 Have to be placed so that they are not covered in any way Adequate fresh air flow can also be provided using the opening to the next room if the room is equipped with direct ventilation a...

Страница 11: ...I Maximum height of the pipe which is connected directly to the smoke outlet in the furnace should be between 2 to 3 m If you need a horizontal segment ensure that it does not exceed 1 5 m in length a...

Страница 12: ...er resistance to atmospheric conditions as well as the proper temperature of exhaust gases themselves 2 2 2 Smoke outlet at the roof through the traditional chimney Exhaust gases from the furnace can...

Страница 13: ...ring first ignition Check whether all safety requirements have been met see section 1 8 Connect the device to the power supply only when you are sure that the supply voltage is 230 V 50 Hz When you co...

Страница 14: ...ace an advanced control system is installed which provides a safe efficient and reliable management of the operation and maximum functional use of the furnace It is characterised by Simplicity of sett...

Страница 15: ...escription System condition Code Safety error safety thermostat signals when the system is off Block Er01 Safety error pressure control signals only if the combustion fan is turned on Block Er02 Shutt...

Страница 16: ...bmenu Combustion Management Combustion management Power In this sub menu it is possible to modify the system combustion power Use the P4 and P5 buttons to select from 5 powers Power 1 Power 2 Power 3...

Страница 17: ...the P1 button Disabled Daily Weekly Week End Chrono Program Chrono program provides three types of programming Daily weekly and weekend After entering the Chrono program the following message appears...

Страница 18: ...sible to choose between programs Mon Fri Sat Sun The selected programs will be active for the days from Monday to Friday or Saturday and Sunday The programs are activated and deactivated in the same w...

Страница 19: ...ue gas motor are active Ignition Fixed Phase This phase represents a fixed time period that lasts 180 seconds and in case the requirements for the ignition of the furnace are reached before the expira...

Страница 20: ...ge Er11 indicating that the DATE TIME is not accurate Deblock using the P1 button the value of TIME flashes signalling the need for updating the TIME and DATE with the function CLOCK 4 6 2 Pellet feed...

Страница 21: ...of pellet in the burning unit is too low or too high Wait for the furnace to extinguish and then press and hold P2 button for more than 3 seconds Check the size of the pellet Check the cleanliness of...

Страница 22: ...not achieved The presence of some large obstacle or debris in the pipe for entry of primary air Wait for the furnace to extinguish and then press and hold P2 button for more than 3 seconds Check and...

Страница 23: ...tenance of the furnace ATTENTION Each cleaning activity has to be performed when the furnace is completely cold and disconnected from the power supply with the cable pulled out from the socket Number...

Страница 24: ...ties Type 2 must be carried out at about 350 400 hours or else after about 500 600 kg of fuel ATTENTION Each cleaning activity has to be performed when the furnace is completely cold and disconnected...

Страница 25: ...can be removed These parts usually must be replaced every three years depending on the type of furnace the intensity of use etc Seals must be elastic at touch and must be replaced if they become tota...

Отзывы: