background image

 

Picture 2.3:Exhaust duct 

 

The room in which heating body will be mounted should not have aspirators because they can reduce pressure in the 

environment.

 

It is strictly forbidden to close all the air openings.

 

The exhaust duct should be cleaned at least once a year; we recommend that you perform a thorough cleaning of the 

exhaust channel and its connection.

 

After a period of not being used and before the activation, check whether there are any obstructions 

 

 ATTENTION: The exhaust duct has to be built in accordance with the provisions of the standard

.

 

 ATTENTION: Use the adequate tool to check whether the chimney has the minimal suction power of 10 Pa.

 

 

 

2.2.1

 

The smoke exhaust towards the  outer wall 

One solution that can be used includes placing the pellet furnace near the outer wall of the house so that the exhaust 

gases are released directly to the outside (Figure 2.4). Some of the notes set forth by the standard for this type of system 
configurations are listed below:

 

Always make sure that there is a valve for inspection (i) to enable regular cleaning procedures and removal of 

moisture that can form;

 

The end element on the chimney (T) has to be such to be wind and water resistant;

 

Please note that the pipe is properly insulated in the section that passes through the wall.

 

If the pipe for the removal of exhaust gases is located outside, it must be made of double wall and stainless steel to 

provide greater resistance to atmospheric conditions, as well as the proper temperature of exhaust gases themselves. 

 

2.2.2.

Smoke outlet at the roof through the traditional chimney

 

Exhaust  gases  from  the  furnace  can  be  removed  via  a  traditional  chimney  already  built  (Figure  2.5),  if  it  meets  the 

standards required. The standard highlights the main characteristics of a good chimney (C), which are summarised below:

 

Proper insulation, before most in the outer part exposed to atmospheric conditions;

 

The constant inner radius (no segments with smaller radius);

 

It must be made of a material which is resistant to high temperatures, the effects of the combustion products 

and to the corrosive effects of moisture which may occur;

 

Generally in the vertical position, without departing from the vertical angles greater than 45 °.

 

It is recommended that the base of the chimney to be equipped with a chamber for collecting of solid matter i.e. 

moisture (R). The chamber has to be accessible through air-tight door (I).

 

 
 

H>0.50m  

 

 

 

 

 

H>0.50m 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 
 

 

 

 

 

Picture 2.4:The smoke exhaust towards the outer wall

 

Figure 2.5:Smoke outlet at the roof through  

 

 

 

the traditional chimney

 

 

It is recommended to follow the guidelines laid down by standards in relation to the size and radius of the chimney (C). 

In any case, never use exhaust duct with internal radius of less than 100 mm.

 

In the case of exhaust ducts of larger radius, a steel pipe (A) has to be placed inside the chimney bricks or mortar (C), 

as shown in Figure 2.6. 

Steel pipe must be isolated by a suitable heat-resistant materials, such as rock wool or vermiculite (B), and must be 

separated from the outer edge of the chimney. 

 
 
 

Содержание LUCA S

Страница 1: ...his user manual is an integral part of the product It has to be kept and read carefully METAL INDUSTRY VRANJE st Radni ka n 1 PELLET STOVE LUCA S LUCA S8 INSTRUCTIONS FOR ASSEMBLY USE AND MAINTENANCE...

Страница 2: ...ommissioning is performed by qualified personnel Do not use any flammable liquids for the ignition process This product should not be used by people with reduced physical sensory and mental abilities...

Страница 3: ...essary controls and checks for first ignition 9 3 2Fuel feed 9 4 Furnace management system 10 4 1Electric wiring scheme 10 4 2The control panel display use and functions 11 4 2 1 Display K100 11 4 2 2...

Страница 4: ...oblems and solutions 17 5 STOVE MAINTENANCE 18 5 1Routine maintenance 18 5 1 1 CLEANING OF THE DISPLAY AND PARTS OF THE EXTERNAL INSULATION 18 5 1 2 CLEANING OF THE CERAMIC GLASS 18 5 1 3 ROUTINE MAIN...

Страница 5: ...gher level and so as to improve the final product Seals which provide sealing of the combustion chamber must be periodically inspected to prevent undesirable combustion which may occur due to excessiv...

Страница 6: ...3 2 7 Emission of CO at 13 of oxygen 0 0136 0 0213 Efficiency 85 57 92 27 Rated electric energy W 380 Rated voltage V 230 Rated frequency Hz 50 Fuel Pellet Fuel consumption per hour kg h 1 608 0 642...

Страница 7: ...to 8 mm in the radius Wood pellets are primarily characterised by low humidity below 12 and high density 600 kg m3 as well as by its uniformity and compactness which gives this type of fuel high calor...

Страница 8: ...by the manufacturer may lead to failure of the furnace and may void the warranty When feeding the pellets be careful the pellet does not fall into another internal part of the furnace other than the s...

Страница 9: ...he product is equipped with the following safety devices Thermostat for determining the temperature of the tank This device shuts down operation of the product each time the set safety limit is exceed...

Страница 10: ...diminished 4 Have to be placed so that they are not covered in any way Adequate fresh air flow can also be provided using the opening to the next room if the room is equipped with direct ventilation a...

Страница 11: ...I Maximum height of the pipe which is connected directly to the smoke outlet in the furnace should be between 2 to 3 m If you need a horizontal segment ensure that it does not exceed 1 5 m in length a...

Страница 12: ...er resistance to atmospheric conditions as well as the proper temperature of exhaust gases themselves 2 2 2 Smoke outlet at the roof through the traditional chimney Exhaust gases from the furnace can...

Страница 13: ...ring first ignition Check whether all safety requirements have been met see section 1 8 Connect the device to the power supply only when you are sure that the supply voltage is 230 V 50 Hz When you co...

Страница 14: ...ace an advanced control system is installed which provides a safe efficient and reliable management of the operation and maximum functional use of the furnace It is characterised by Simplicity of sett...

Страница 15: ...escription System condition Code Safety error safety thermostat signals when the system is off Block Er01 Safety error pressure control signals only if the combustion fan is turned on Block Er02 Shutt...

Страница 16: ...bmenu Combustion Management Combustion management Power In this sub menu it is possible to modify the system combustion power Use the P4 and P5 buttons to select from 5 powers Power 1 Power 2 Power 3...

Страница 17: ...the P1 button Disabled Daily Weekly Week End Chrono Program Chrono program provides three types of programming Daily weekly and weekend After entering the Chrono program the following message appears...

Страница 18: ...sible to choose between programs Mon Fri Sat Sun The selected programs will be active for the days from Monday to Friday or Saturday and Sunday The programs are activated and deactivated in the same w...

Страница 19: ...ue gas motor are active Ignition Fixed Phase This phase represents a fixed time period that lasts 180 seconds and in case the requirements for the ignition of the furnace are reached before the expira...

Страница 20: ...ge Er11 indicating that the DATE TIME is not accurate Deblock using the P1 button the value of TIME flashes signalling the need for updating the TIME and DATE with the function CLOCK 4 6 2 Pellet feed...

Страница 21: ...of pellet in the burning unit is too low or too high Wait for the furnace to extinguish and then press and hold P2 button for more than 3 seconds Check the size of the pellet Check the cleanliness of...

Страница 22: ...not achieved The presence of some large obstacle or debris in the pipe for entry of primary air Wait for the furnace to extinguish and then press and hold P2 button for more than 3 seconds Check and...

Страница 23: ...tenance of the furnace ATTENTION Each cleaning activity has to be performed when the furnace is completely cold and disconnected from the power supply with the cable pulled out from the socket Number...

Страница 24: ...ties Type 2 must be carried out at about 350 400 hours or else after about 500 600 kg of fuel ATTENTION Each cleaning activity has to be performed when the furnace is completely cold and disconnected...

Страница 25: ...can be removed These parts usually must be replaced every three years depending on the type of furnace the intensity of use etc Seals must be elastic at touch and must be replaced if they become tota...

Отзывы: