71
Parameter:
Fan MIN. time OFF
Code:
TEMP_2
Units:
Description:
Minimum stop time for the condenser fans.
This parameter is useful for preventing an excessive number of fan starts and stops.
Parameter:
Fan ON-ON Delay Slow
Code:
TEMP_3
Units:
Description:
Minimum time between start ups of different fans within the slow control
zone.
Adjustment of this parameter is very important in defining dynamic control of
the fans:
Neutral Zone or Proportional Band
For further information, see
Chapter 5.
Parameter:
Fan OFF-OFF Delay Slow
Code:
TEMP_4
Units:
Description:
Minimum time between shutdowns of different fans within the slow control
zone.
Adjustment of this parameter is very important in defining dynamic control of
the fans:
Neutral Zone or Proportional Band
For further information, see
Chapter 5.
Parameter:
Fan ON-ON Delay Fast
Code:
TEMP_5
Units:
Description:
Minimum time between start ups of different fans within the fast control
zone.
Adjustment of this parameter is very important in defining dynamic control of
the fans:
Neutral Zone or Proportional Band
For further information, see
Chapter 5.
Seconds
Seconds
Seconds
Seconds
we make it easy
Содержание AKO-21006
Страница 20: ...20 The digital inputs and outputs from the above example are connected as follows B A B a a we make it easy...
Страница 104: ...104 A 5 Physical dimensions AKO 21801 AKO 21802 AKO 21803 67 mm 52 mm 51 mm 280 mm 90 mm DUOVision we make it easy...
Страница 117: ...NOTES 117 we make it easy...
Страница 118: ...118 NOTES we make it easy...
Страница 119: ...NOTES 119 we make it easy...