73
Parameter:
Compr. OFF-OFF Delay Slow
Code:
TEMP_10
Units:
Description:
Minimum time between shutdowns of different compressor stages in the
slow control zone.
Adjustment of this parameter is very important in defining dynamic control of
the compressors:
Neutral Zone or Proportional Band
For further information, see
Chapter 4.
Parameter:
Compr. ON-ON Delay Fast
Code:
TEMP_11
Units:
Description:
Minimum time between the starting of different compressor stages in the
fast control zone.
Adjustment of this parameter is very important in defining dynamic control of
the compressors:
Neutral Zone or Proportional Band
For further information, see
Chapter 4.
Parameter:
Code:
TEMP_12
Units:
Description:
Minimum time between shutdowns of different compressor stages in the
fast control zone.
Adjustment of this parameter is very important in defining dynamic control of
the compressors:
Neutral Zone or Proportional Band
For further information, see
Chapter 4.
Seconds
Seconds
Seconds
Compr. OFF-OFF Delay Fast
IMPORTANT:
The
8
icon indicates that the data is being saved. If the equipment is disconnected
or the power supply fails while this icon is showing, the equipment will return to the last saved
configuration.
we make it easy
Содержание AKO-21006
Страница 20: ...20 The digital inputs and outputs from the above example are connected as follows B A B a a we make it easy...
Страница 104: ...104 A 5 Physical dimensions AKO 21801 AKO 21802 AKO 21803 67 mm 52 mm 51 mm 280 mm 90 mm DUOVision we make it easy...
Страница 117: ...NOTES 117 we make it easy...
Страница 118: ...118 NOTES we make it easy...
Страница 119: ...NOTES 119 we make it easy...