The activation/deactivation points
for the compressors or stages are:
Stage
1ª
2ª
3ª
4ª
5ª
6ª
Start
-13ºC
-12ºC
-11ºC
-10ºC
-9ºC
-8ºC
Stop
-14ºC
-13ºC
-12ºC
-11ºC
-10ºC
-9ºC
The control action depends on the suction probe reading in the following way:
Within the PROPORTIONAL BAND:
the minimum time interval between startups of compressors
or stages is defined by the parameter
TEMP_9,
while the minimum time interval between
shutdowns of compressors or stages will be defined by the parameter
TEMP_10.
Within the POSITIVE SLOW ZONE:
the time between startups of compressors or stages is defined
by the parameter
TEMP_9.
Within the POSITIVE FAST ZONE:
the time between startups of compressors or stages is defined
by the parameter
TEMP_11.
Within the NEGATIVE SLOW ZONE:
the time between shutdowns of compressors or stages is
defined by the parameter
TEMP_10.
Within the NEGATIVE FAST ZONE:
the time between shutdowns of compressors or stages is
defined by the parameter
TEMP_12.