Example:
Compressor facility with 3 x 2-stage compressors.
EVAPORATION SP (EVAP_1):
-10ºC
POSITIVE SLOW ZONE DIFFERENTIAL WITH RESPECT TO EVAP_SP (EVAP_6):
2ºC
NEGATIVE SLOW ZONE DIFFERENTIAL WITH RESPECT TO EVAP_SP (EVAP_7):
4ºC
The start/stop points for the compressors or stages will be located at the following evaporation
pressure levels:
Pevap (bar)
Tevap (ºC)
EVAP_6=2ºC
EVAP_1=-10ºC
EVAP_7=4ºC
-8ºC
-9ºC
-10ºC
-11ºC
-12ºC
-13ºC
-14ºC
No. of ACTIVE
STAGES
6 Stages
5 Stages
4 Stages
3 Stages
2 Stages
1 Stage
0 Stages
( EVAP_7)
(CONF_1 x CONF_2)
t
86