According to CONF_8 parameter
59
Parameter:
Negative Differential Fast Zone
Code:
COND_8
Units:
Description:
Bandwidth of the NEGATIVE FAST ZONE used in the definition of the algorithms for
controlling the condensation circuit. For further information, see
Chapter 5.
Parameter:
Activate Floating Cond.
Code:
COND_9
Description:
Activation/Deactivation of floating condensation. To activate this functionality it is
essential to have the Ambient air temperature probe installed.
NO:
Do not activate floating condensation
YES:
Activate floating condensation
For further information, see
Chapter 5.
Parameter:
Proportional value
Code:
COND_10
Description:
Adjustment of the PI control proportional value to regulate the 4-20 mA output for the
inverter for the condenser fans. For further information, see
Chapter 5.
Parameter:
Integrative value
Code:
COND_11
Description:
Adjustment of the PI control integrative value to regulate the 4-20 mA output for the
inverter for the condenser fans. For further information, see
Chapter 5.
IMPORTANT:
The
8
icon indicates that the data is being saved. If the equipment is disconnected
or the power supply fails while this icon is showing, the equipment will return to the last saved
configuration.
we make it easy
Содержание AKO-21006
Страница 20: ...20 The digital inputs and outputs from the above example are connected as follows B A B a a we make it easy...
Страница 104: ...104 A 5 Physical dimensions AKO 21801 AKO 21802 AKO 21803 67 mm 52 mm 51 mm 280 mm 90 mm DUOVision we make it easy...
Страница 117: ...NOTES 117 we make it easy...
Страница 118: ...118 NOTES we make it easy...
Страница 119: ...NOTES 119 we make it easy...