69
Parameter:
Start - Hour
Code:
AENR_2
Units:
Description:
Hour for starting the Energy Saving function.
Parameter:
Start - Minutes
Code:
AENR_3
Units:
Description:
Minutes for starting the Energy Saving function.
Parameter:
Energy Saving Duration
Code:
AENR_4
Units:
Description:
Duration of the Energy Saving function.
Parameter:
Evap. Diff. Energy Saving
Code:
AENR_5
Units:
Description:
The value of this parameter added to the Evaporation Set Point (EVAP_1)
gives the Set Point during the Energy Saving function.
Example:
Let us consider an installation with an:
EVAPORATION SP =
-10ºC (EVAP_1)
where we wish to configure Energy Saving functionality in the following way: To start the Energy
Saving function on Fridays at 10:15 pm for a duration of 20 hours.
Evaporation Set Point during Energy Saving:
0ºC
With these requirements, the related user parameters will be configured using the following values:
AENR_1 = Friday
AENR_2 = 22 hours
AENR_3 = 15 minutes
AENR_4 = 20 hours
AENR_5 = +10ºC
EVAP_1 Evaporation SP
Evaporation Set Point during Energy Saving
AENR_5 Differential during Energy Saving
According to CONF_8 parameter
Hours
Minutes
Hours
IMPORTANT:
The
8
icon indicates that the data is being saved. If the equipment is disconnected
or the power supply fails while this icon is showing, the equipment will return to the last saved
configuration.
we make it easy
Содержание AKO-21006
Страница 20: ...20 The digital inputs and outputs from the above example are connected as follows B A B a a we make it easy...
Страница 104: ...104 A 5 Physical dimensions AKO 21801 AKO 21802 AKO 21803 67 mm 52 mm 51 mm 280 mm 90 mm DUOVision we make it easy...
Страница 117: ...NOTES 117 we make it easy...
Страница 118: ...118 NOTES we make it easy...
Страница 119: ...NOTES 119 we make it easy...