2.3.1.- FIXED WIRING TERMINALS
The recommended wiring for the fixed wiring terminals is shown below:
The general high and low pressure switchs are connected to terminals
I1
and
I2
respectively. The type of
contact for each of these inputs can be configured by means of the user parameters
ENTR_1
and
ENTR_2.
For further information, see
Section 3.3.6.
The
MANUAL/AUTOMATIC
selector is connected to terminal
I3.
MANUAL: Voltage of +24 V in terminal I3.
AUTOMATIC: Voltage of 0 V in terminal I3.
Their function is described in
Section 7.4.
Terminals connected to a cross have no function allocated and are not connected.
The terminals not yet connected are dealt with in the next section.