Operating the LCD
©Aqua-Hot®
250-D03 Diesel Series Service Manual
REV 220302
p. 8
Operational Flow Chart
Operational Flow Chart
A heat source is selected from
Interior Control Panel
Electric Element
Electric Heating Element
will activate, providing
heat to the antifreeze and
water heating solution
within the boiler tank
The burner will begin
providing heat to the
antifreeze and water heating
solution present within the
boiler tank.
The antifreeze and water
heating solution in the boiler
tank heats to 180°F
An Interior Zone
Thermostat Calls
for Heat
A hot water faucet opens,
signaling a need for heat to the
boiler tank
The fluid circulation pump
activates and begins circulating
the heated antifreeze and water
solution throughout the interior
heating zone
The heating zone
fans activate
Heat is transferred to the
vehicle interior via the heat
exchangers
The cooled antifreeze
is returned to the boiler
tank to be reheated.
Hot water flows from the water
faucet
Heat is transferred to the
domestic hot water system
Diesel Burner
NOTE:
The Burner
and/or Electric
Element (as turned
ON) will automatically
begin reheating the
antifreeze and water
heating solution when
the boiler tank drops
below 155°F.