OPTIONAL ACCESSORIES
13-26
Revision 0
Service Manual - KXL DCI
13.3.4
Outdoor Unit Diagnostics and Corrective Actions
N
Fault
Probable Cause
Corrective Action
1
Sensors failures of
all types
Check
sensors
connections or replace
sensors.
2
IPM Fault
Electronics HW
problem
Check all wiring and
jumper settings, if OK,
replace electronics.
3
Bad EEPROM
No action, unless
special parameters
are required for unit
operation.
4
DC under/over
Voltage
Electronics HW
problem
Check outdoor unit
power supply voltage
5
AC under Voltage
Check outdoor unit
power supply voltage
6
Indoor / Outdoor unit
Communication
mismatch
Indoor and
Outdoor
controllers are
with different
versions
Replace Indoor
controller
7
No Communication
Communication or
grounding wiring is
not good.
Check Indoor to
Outdoor wiring and
grounding
8
Compressor Lock
Switch unit to STBY
and restart
9
Bad Communication
Communication
quality is low
reliability
Check Indoor to
Outdoor wiring and
grounding
Содержание GC 24 DCI