Service Manual - KXL DCI
12-13
12.10.2 Outdoor Unit controller Indicatiors
Unit has three LED’s.
SB LED is ON when power is ON (230 VAC, even when no communication).
STATUS LED is ON when COMP is ON, and Blinks according to diagnostics mode definitions
when either fault or protection occurs.
FAULT LED Blinks according to diagnostics mode definitions when either fault or protection
occurs.
12.11 Jumper
Settings
12.11.1 Indoor Unit Controller
0 = Open Jumper (disconnect jumper).
1 = Close Jumper (connect jumper).
Self test Jumper – J1
OPERATION J1
SELF-TEST 1
NORMAL 0
Compensation Jumper – J2
Model J2
(Default)
Compensation
WNG/WNG18/WNG30/WSA 0
Activated
PXD/AC/NPXD 1
Deactivated
LS/K/KS/AS/AD/DNG/KN 1
Activated
Family selection Jumper – J3, J4 ,J5and J6
Family
J6
J5
J 4 J3
AS
AC
AD
WNG
PXD
KS
LS
K
WNG18
WNG30
Delta 50
WSA
DNG
KN
NPXD
Reserved
0 0
0
0
0
0
0 1
0
0
1 0
0
0
1 1
0 1 0 0
0
1
0 1
0
1
1 0
0 1
1
1
1 0 0 0
1 0 0 1
NA
1 0 1 1
NA
1 1 0 1
NA
1 1 1 1
Содержание GC 24 DCI
Страница 9: ...OUTLINE DIMENTIONS Revision 0 Service Manual KXL DCI 4 2 Outdoor Unit 4 1 1 GC 24 30 DCI...
Страница 25: ...REFRIGERATION DIAGRAMS 9 2 Revision 0 Service Manual KXL DCI 9 2 1 GC 24 30 DCI...
Страница 26: ...Service Manual KXL DCI 10 3 10 REFRIGERATION DIAGRAMS 10 1 Cooling mode 10 2 Heating mode EEV EEV...