Service Manual - KXL DCI
12-15
12.11.3.2 Outdoor
Unit
Controller For GC 24/30 DCI
OFAN Jumpers
OFAN use parameters
J2
J1
Panasonic- EHD80 (ROM)
0
0
Nideq OFAN (ROM)
0
1
Shinano (ROM)
1
0
EEPROM 1
1
Compressor Jumpers
Compressor use parameters
J3
TNB220 (ROM)
0
EEPROM 1
12.12 Test
Mode
12.12.1 Entering Test Mode
System can enter Test mode in two ways:
Automatically when the following conditions exists for 30 minutes continuously:
Mode = Cool, Set point = 16, Room temperature = 27
(+1/−2)
, Outdoor temperature = 35(+2/-1)
Or
Mode = Heat, Set point = 30, Room temperature = 20±1, Outdoor temperature = 7±(+1/-2)
Manually when entering diagnostics with the following settings:
Mode = Cool, Set point = 16
Mode = Heat, Set point = 30
12.12.2 Unit Operation in Test Mode
In test mode, the unit will operate in fixed settings according to the indoor fan speed setting:
Indoor FAN Speed Setting
Unit Setting
Low Minimum
Capacity
Setting
Turbo
Nominal Capacity Setting
Auto
Maximum Capacity Setting
During test mode, protections are disabled, except for stop compressor status.