PERFORMANCE DATA
5-6
Revision 0
Service Manual - KXL DCI
5.2.3
Heating Capacity (kW)-Run Mode
ID COIL ENTERING AIR DB TEMPERATURE [C
0
]
OD COIL
ENTERING AIR
DB/WB
TEMPERATURE
[C
0
]
DATA 15
20
25
TC 4.10
3.51 2.92
-15/-16
PI 1.82
1.95 2.08
TC 5.41
4.82 4.23
-10/-12
PI 2.06
2.19 2.32
TC 6.39
5.80 5.21
-7/-8
PI 2.23
2.36 2.49
TC 6.88
6.29 5.70
-1/-2
PI 2.32
2.45 2.58
TC 7.21
6.62 6.03
2/1
PI 2.38
2.51 2.64
TC 9.59
9.00 8.41
7/6
PI 2.47
2.60 2.73
TC 10.09
9.50 8.91
10/9
PI 2.52
2.65 2.78
TC 10.58
9.99 9.40
15/12
PI 2.57
2.70 2.83
15-24
TC
85 - 105 % of nominal
(Protection Range)
PI
80 - 120 % of nominal
5.2.4 Capacity
Correction Factors
Heating Capacity Ratio Vs. Outdoor Temperature
0.4
0.5
0.6
0.7
0.8
0.9
1
1.1
1.2
-15
-10
-5
0
5
10
15
Outdoor WB Temperature [deg C]
Capaci
ty
Rat
ion