Service Manual - KXL DCI
13-19
No
SYMPTOM PROBABLE
CAUSE
CORRECTIVE ACTION
5
Indoor fan works
when unit is OFF,
and indoor fan speed
is not changed by
remote control
command.
PCB problem
Replace controller
6
Compressor does not
start
Electronics
control problem
or protection
Perform diagnostics (See 13.3
below), and follow the actions
described.
7 Compressor
stops
during operation and
Green LED remains
on
Electronic
control or power
supply problem
Perform diagnostics (See 13.3
below), and follow the actions
described.
8
Compressor is on but
outdoor fan does not
work
Problem with
outdoor
electronics or
outdoor fan
Check outdoor fan motor
according to the procedure in
section 13.5.3 below, if not OK
replace controller
9
Unit works in wrong
mode (cool instead of
heat or heat instead
of cool)
Electronics or
power
connection to
RV
Check RV power connections, if
OK,
Check RV operation with direct
230VAC power supply, if OK,
Replace outdoor controller.
10
All components are
operating properly
but no cooling or no
heating
Refrigerant leak
Check refrigeration system.
11
Compressor is over
heated and unit does
not generate capacity
EEV problem
Check EEV
12
Units goes into
protections and
compressor is
stopped with no clear
reason
Control problem
or refrigeration
system problem
Perform diagnostics (See 13.3
below), and follow the actions
described.
13
Compressor motor is
generating noise and
no suction occurs
Phase order to
compressor is
wrong
Check compressor phase order.
14
Water leakage from
indoor unit
Indoor unit
drainage tube is
blocked
Check and open drainage tube.
15 Freezing
of
outdoor
unit in heat mode
and outdoor unit
base is blocked with
ice
Connect base heater.