OPTIONAL ACCESSORIES
13-28
Revision 0
Service Manual - KXL DCI
13.6
Precaution, Advise and Notice Items
13.6.1
High voltage in Outdoor unit controller.
Whole controller, including the wires that are connected to the Outdoor unit controller may
have the potential hazard voltage when power is on. Touching the Outdoor unit controller
may cause an electrical shock.
Advise:
Don’t touch the naked lead wire and don’t insert finger, conductor or anything
else into the controller when power is on.
13.6.2 Charged
Capacitors
Three large-capacity electrolytic capacitors are used in the Outdoor unit controller.
Therefore, charging voltage (380VDC) remains after power down. Discharging takes
about four minutes after power is off. Touching the Outdoor unit controller before
discharging may cause an electrical shock.
13.6.3 Additional
advises
z
When disassemble the controller or the front panel, turn off the power supply.
z
When connecting or disconnecting the connectors on the PCB, hold the whole
housing, don’t pull the wire.
z
There are sharp fringes and sting on shell. Use gloves when disassemble the A/C
units.
Содержание GC 24 DCI
Страница 9: ...OUTLINE DIMENTIONS Revision 0 Service Manual KXL DCI 4 2 Outdoor Unit 4 1 1 GC 24 30 DCI...
Страница 25: ...REFRIGERATION DIAGRAMS 9 2 Revision 0 Service Manual KXL DCI 9 2 1 GC 24 30 DCI...
Страница 26: ...Service Manual KXL DCI 10 3 10 REFRIGERATION DIAGRAMS 10 1 Cooling mode 10 2 Heating mode EEV EEV...