4. Operation
4
-
8
4.5.2 How to connect single phase load
The method of connection of 3 phase 4 wire single phase load is as follows.
The allowable current limit shall not exceed the values in the following table.
Conditions of Load
Allowable Current Limit
Conditions
In case of three phases
Allowable current limit up to
the rated current.
Adjust the load capacity so that
each current value of each phase
(U,V,W) may not be more un-
balanced than 50%.
In case of using 2 phas
es
In case of using single phase
Type
Permissible
current value
50Hz/200V
144A
60Hz/220V
157A
50Hz/380V
76.0A
50Hz/400V
72.2A
50Hz/415V
69.6A
60Hz/440V
78.7A
Allowable current limit up to
the rate current.
But voltage change becomes
larger due to the unbalance of
each phase.
In case of three phases
Allowable current limit up to
the rated current.
Adjust the load capacity, so that
each current value of each phase
(U,V,W) may not be more un-
balanced than 50%.
3 Phase 4 W
ire Typ
e
In case of using O phas
e
In case of using single phase
Type
Permissible
current value
50Hz/115V
(200V)
144A
60Hz/127V
(220V)
157A
50Hz/219V
(380V)
76.0A
50Hz/231V
(400V)
72.2A
50Hz/240V
(415V)
69.6A
60Hz/254V
(440V)
78.7A
Allowable current limit up to
the rated current.
Bur the voltage change becomes
larger due to the unbalance of
each phase.
Содержание SDG60S-7A6
Страница 1: ......
Страница 12: ...2 Part Names 2 1 2 1 Internal Components A070010 1 1 2 3 4 5 6 7 8 9 10 16 15 14 13 12 11...
Страница 56: ...8 Specifications 8 2 8 2 Outline drawing A060509E 1...
Страница 57: ...9 Wiring Diagram 9 1 9 1 Generator Wiring Diagram A050635E...
Страница 58: ...9 Wiring Diagram 9 2 9 2 Engine Wiring Diagram A070003E...
Страница 59: ...10 Piping Diagram 10 1 10 1 Fuel piping A070103E 1...
Страница 61: ......