4. Operation
4
-
7
Install a switch between the output terminal and
the load to switch on/off the load. Do not switch the
load on/off directly by the circuit-breaker of the
machine.
It could cause damage to the Connect the connect-
ing cable to the load so that the output terminals
should not touch each other. circuit-breaker.
4.5.1
How to connect three phase load
In case of three-phase load:
Each electric current value of each phase (U.V.W)
should not exceed the values in the following table.
Type
Permissible current value
50Hz/200V 144A
60Hz/220V 157A
50Hz/380V 76.0A
50Hz/400V 72.2A
50Hz/415V 69.6A
60Hz/440V 78.7A
In case inverter load:
The inverter capacity (input kVA of inverter) should not exceed the following value
(within rated output
÷
3.0). Also select generator so that the rated output (kVA) of generator
so that the rated output (kVA) of generator may be three times of the inverter capacity.
Example: In case of SDG60S,at 50Hz, 50kVA
÷
3.0 = 16.7kVA.
50Hz: 16.7kVA (Input kVA of inverter) It is possible to use inverter capacity up to this value.
60Hz: 20.0kVA (Input kVA of inverter) It is possible to use inverter capacity up to this value.
A050317
Switch panel for
switching on/off load
SG0114-1
Load
Содержание SDG60S-7A6
Страница 1: ......
Страница 12: ...2 Part Names 2 1 2 1 Internal Components A070010 1 1 2 3 4 5 6 7 8 9 10 16 15 14 13 12 11...
Страница 56: ...8 Specifications 8 2 8 2 Outline drawing A060509E 1...
Страница 57: ...9 Wiring Diagram 9 1 9 1 Generator Wiring Diagram A050635E...
Страница 58: ...9 Wiring Diagram 9 2 9 2 Engine Wiring Diagram A070003E...
Страница 59: ...10 Piping Diagram 10 1 10 1 Fuel piping A070103E 1...
Страница 61: ......