6. Maintenance/Adjustment
6
-
4
Symptom Cause Counter
measures
Even when
operated at a rated
speed, no voltage or
too low voltage
generated.
(1) Faulty voltmeter
(2) Poor tightening of terminals
(3) Broken or short-circuited winding of
generator main unit
(4) Faulty AVR
(5) Faulty silicon rectifier (mounted on
generator main unit rotor)
(6) Faulty exciter
(7) Broken or short-circuited circuit to
exciter field winding
(8) AVR frequency selection switch is not set
to meet the frequency to be operated.
(9) Function circuit protector (CP) for AVR
protection
Check/change
Check/repair
Check/repair
Check/change
Check/change
Check/repair
Check/repair
Check/select
Reset
Too high voltage
generated when set
at the rated
frequency
(50Hz/60Hz),
Voltage will not
drop even when the
voltage regulator
controlling knob is
turned.
(1) Loosened or disconnected wiring, or
connector to AVR
(2) Faulty AVR
(3) Broken wire or poor contact of AVR
variable resistor
Check/repair
Check/change
Repair or change
Unstable voltage
generation
(1) Poor tightening of each terminal
(2) Faulty AVR
(3) Function circuit protector (CP) for AVR
protection
Check/repair
Check/change
Reset
Please contact your nearest dealer if you find it difficult to repair by yourselves.
Please refer to the engine operation manual for troubles concerning the engine.
Содержание SDG60S-7A6
Страница 1: ......
Страница 12: ...2 Part Names 2 1 2 1 Internal Components A070010 1 1 2 3 4 5 6 7 8 9 10 16 15 14 13 12 11...
Страница 56: ...8 Specifications 8 2 8 2 Outline drawing A060509E 1...
Страница 57: ...9 Wiring Diagram 9 1 9 1 Generator Wiring Diagram A050635E...
Страница 58: ...9 Wiring Diagram 9 2 9 2 Engine Wiring Diagram A070003E...
Страница 59: ...10 Piping Diagram 10 1 10 1 Fuel piping A070103E 1...
Страница 61: ......