Chapter 5
Running an Autotest 58
Diagnostics
The Diagnostics section of the DualRemote 350 front panel provides more
detailed information about failing test results.
WS and DR LEDs indicate at which end of the tested cable the measurement
failed.
A column of diagnostic LEDs provide further detail about the cause(s) of a test
failure. The failure causes that can be indicated are:
·
Wiremap
·
Split pairs
·
Length / Delay / Skew (any of these conditions)
·
NEXT (pair-to-pair or power sum)
·
Attenuation
·
ELFEXT (pair-to-pair or power sum)
·
Return Loss
·
Other (any other failing measurement)
In the event that the cabling run has multiple test failure causes (i.e. NEXT and
Return Loss), you can use the
key to scroll between failure cause indications.
The current selection is indicated by a blinking LED. The pair indicators and
WS/DR indicators will blink to show which pairs and which cable end
correspond to the selected failure cause.
Power LED
The power LED indicates on / off status for the DualRemote 350. When this
LED is lit, the DualRemote 350 is powered on.
Test failed at
WireScope end of
cabling run
Test failed at
DualRemote end of
cabling run
Test failed at both
ends of cabling run
Содержание WireScope 350
Страница 1: ...www wirescope com W i r e S c o p e 3 5 0 U s e r s G u i d e...
Страница 13: ...Chapter 1 Introduction 12...
Страница 17: ...Chapter 2 Cable Testing Overview 16...
Страница 45: ...Chapter 4 Preparing to Run an Autotest 44...
Страница 63: ...Chapter 6 Certify Networks 62...
Страница 69: ...Chapter 7 Tools 68...
Страница 99: ...Chapter 11 Running Fiber Autotest 98...
Страница 103: ...Chapter 12 Fiber Certify Networks 102...
Страница 111: ...Chapter 13 Fiber Tools 110...
Страница 137: ...Chapter 16 Using the Talkset Option 136...
Страница 149: ...Appendix C Legacy Networks 148...
Страница 153: ...Appendix D Battery information 152...