7713397 R2
81
Single Phase (1P) Wiring (Without VFD)
1. Connect wires T1 and T2 into the bottom of the respective starter(s). Note that T3 loops from the lower-
middle position back up to the upper-right position to provide internal feedback within the control system.
2. Connect the green ground wire to the ground terminal in the control box.
Three Phase (3P) Wiring (Without VFD)
1. Connect wires T1, T2, and T3 into the bottom of the respective starter(s).
2. Connect the green ground wire to the ground terminal in the control box.
Figure 94.
Blower Motor Wiring
L1
L2
L3
SINGLE PHASE (1P)
MOTOR STARTER
T1
T3
T2
BLOWER #
MOTOR
STARTER
THREE PHASE (3P)
MOTOR STARTER
T1 T2
T3
L1
L2
L3
BLOWER #
MOTOR
STARTER
SINGLE PHASE
THREE PHASE
Single or Three Phase Wiring (With VFD)
Connect wires in VFD enclosure(s) and main control panel as indicated in their respective schematics sent with
the dryer.
CONTINUOUS-FLOW GRAIN DRYER – COMMANDER CONTROL