SE-Power FS STO-manual vers. 1.6 en.12.08.2015
57
Cabling
Max. cable length
Unscreened
[m]
30
Screened
[m]
30
Screening
When wiring outside the control cabinet, use screened
cable. Guide screening into the control cabinet / attach
to the side of the control cabinet.
Cable cross section (flexible conductors, wire end sleeve with insulating collar)
One conductor
mm²
0,25 … 0,5
Two conductors
mm²
2 x 0,25 (with twin wire end sleeves)
Tightening torque M2
[Nm]
0,22 … 0,25
Table 26:
Technical data: Cabling to [X40]