The oxygen level at the 30% valve position should be as shown below. Also, ensure that
47.
the carbon monoxide (CO) and nitrogen oxide (NOx) readings do not exceed the values
shown.
Table 4-5: Combustion Oxygen Levels for a
30%
Air/Fuel Valve Position
Oxygen
%
± 0.2
Carbon
Monoxide
NOx
7.0 %
<50 ppm
<30 ppm
If the oxygen level is not within the specified range, adjust the level using the ▲ and ▼
48.
arrow keys. This will adjust the output voltage to the blower motor as indicated on the
display. Pressing the ▲ arrow key increases the oxygen level and pressing the ▼ arrow
key decreases the oxygen level.
Once the oxygen level is within the specified range at 30%, press the ENTER key to
49.
store the selected blower output voltage for the 30% valve position.
Press the ▲ arrow key until
SET Valve Position
appears on the C-MORE display.
50.
Press the CHANGE key.
SET Valve Position
will begin to flash.
51.
Press the ▼ arrow key until the
SET Valve Position
reads
16%
, then press the ENTER
52.
key.
Press the ▼ arrow key until
CAL Voltage 16%
is displayed.
53.
Press the CHANGE key.
CAL Voltage 16%
will begin to flash.
54.
The oxygen level at the 16% valve position should be as shown below. Also, ensure that
55.
the carbon monoxide (CO) and nitrogen oxide (NOx) readings do not exceed the values
shown.
Table 4-6: Combustion Oxygen Levels for a
16%
Air/Fuel Valve Position
Oxygen
%
± 0.2
Carbon
Monoxide
NOx
8.0 %
<50 ppm
<30 ppm
If the oxygen level is not within the specified range, adjust the level using the ▲ and ▼
56.
arrow keys. This will adjust the output voltage to the blower motor as indicated on the
display. Pressing the ▲ arrow key increases the oxygen level and pressing the ▼ arrow
key decreases the oxygen level.
Once the oxygen level is within the specified range at 16%, press the ENTER key to
57.
store the selected blower output voltage for the 16% valve position.
This completes the natural gas combustion calibration procedure.