APPENDIX A
Benchmark 2.0LN Low NOx Boiler
GF-120
MENU ITEMS
Installation, Operation and Maintenance Manual
OMM-0041_0E
Page 112 of 166 AERCO International Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
•
Ph: 800-526-0288
PR1:10/18/12
Table A-1: Boiler Menu Item Descriptions
MENU LEVEL & OPTION
DESCRIPTION
SETUP MENU
Password
Allows password to be entered.
Once the valid password (159) is entered, options in
the Setup, Configuration and Tuning Menus can be
modified.
Language
Permits selection of English, Spanish or French for
displayed messages. Default is English.
Time
Displays time from 12:00 am to 11:59 pm.
Date
Displays dates from 01/01/00 to 12/31/99
Unit of Temp
Permits selection of temperature displays in degrees
Fahrenheit (°F) or degrees Celsius (°C). Default is
°F.
Comm Address
For RS-485 communications (0 to 127). Default
address is 0. RS-232 should have its own
(programmable) password.
Baud Rate
Allows communications Baud Rate to be set (2400
to 19.2K). Default is 9600.
Min Upload Timer
Mandatory for AERCO OnAER Remote Data
Collection (ORDC). This parameter enables ORDC
and defines the minimum amount of time between
heartbeat data uploads in seconds.. The COMM
LED will light during the upload.
Unit Alpha
Mandatory for AERCO OnAER Remote Data
Collection. This value must match the first alpha
digit on the Code Plate. e.g.
G
-12-1234.
Unit Year
Mandatory for AERCO OnAER Remote Data
Collection. This value must match the 2-digit year on
the Code Plate. e.g. G-
12
-1234.
Unit Serial #
Mandatory for AERCO OnAER Remote Data
Collection. This value must match the 4-digit serial #
on the Code Plate. e.g. G-12-
1234.
Software Version
Identifies the current software version of the control
box (Ver 0.0 to Ver 9.9).