CHAPTER 3
OPERATION
Page 44 of 166 AERCO International Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
•
Ph: 800-526-0288
PR1:10/18/12
Benchmark 1.5LN Low NOx Boiler
Installation, Operation and Maintenance Manual
GF-120
OMM-0041 0E
AIR/FUEL
VALVE OUTLET
TO BLOWER
BLOWER
PROOF
SWITCH
Figure 3-5: Blower Proof Switch
25
TO BLOWER
AIR IN
DIAL
(DETAIL “A”)
STEPPER
MOTOR
DETAIL “A”
Figure 3-6: Air/Fuel Valve In Ignition Position
Up to 7 seconds will be allowed for ignition to be detected. The igniter relay will be
6.
turned off one second after flame is detected.