GF-120
Benchmark 1.5LN Low NOx Boiler
APPENDIX E
OMM-0041_0E
I
nstallation
,
Operation and Maintenance Manual
BOILER DEFAULTS
PR1: 10/18/12 AERCO International Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
•
Ph: 800-526-0288
Page 127 of 166
Table E-1: Boiler Default Settings (Continued)
MENU & OPTION
FACTORY DEFAULT
Configuration Menu
- Continued
Aux Start On Dly
0 sec
Failsafe Mode
Shutdown
Analog Output
Valve Position 0-10V
CAUTION: DO NOT Change
Lo Fire Timer
2 sec
Setpt Limit Band (If Setpt Limiting =
Enabled)
5°F
Network Timeout
30 seconds
Hi DB Setpt En
30
Demand Offset
10
Deadband High
2
Deadband Low
2
Spark Monitor
Disabled
Spark Current
0
Tuning Menu
Prop Band
70°F
Integral Gain
1.00
Derivative Time
0.0 min
Warmup Prop Band
95
Warmup Int Gain
50
Warmup PID Timer
20
Reset Defaults
No