CHAPTER 4
INITIAL START-UP
Page 58 of 166 AERCO International Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
•
Ph: 800-526-0288
PR1:10/18/12
Benchmark 1.5LN Low NOx Boiler
Installation, Operation and Maintenance Manual
GF-120
OMM-0041 0E
The digital alarm switch settings can be checked or adjusted using the controls and display on
the front panel of the switch illustrated and described in Figure 4-7 and Table 4-7..
F
Alarm
RST
SET
Limit Control
Figure 4-7: Digital Alarm Switch Front Panel
Table 4-6: Digital Alarm Switch Controls and Display
CONTROL or
Display
MEANING
FUNCTION
LED Display
TEMP status
Displays current water temperature or
setpoint.
RST
RESET Button
Resets the unit after an alarm condition.
UP Button
Increases the displayed temperature.
DOWN Button
Decreases the displayed temperature.
SET
SET Button
Used to access and store parameters in the
unit.
Perform the following steps to check or adjust the digital alarm switch settings:
1.
Set the
ON/OFF
to the ON position.
2.
Press the
SET
button on the Digital Alarm Switch.
SP
will appear in the display.
3.
Press the
SET
button again. The current over-temperature limit value stored in memory will
be displayed. (default = 210°F).
4.
If the display does not show the required over-temperature alarm setting, press the ▲ or ▼
arrow button to change the display to the desired temperature setting.