The Operation Time Log can only be accessed through the RS232 interface using a laptop or other
terminal device. Ten operation time records are displayed for each T command entry. The operation
time log can be cleared ONLY by factory authorized personnel using the Clear Log option in the
Factory menu.
NOTE
The Sensor (S) Log can store up to 1200 records. Therefore, to view the most
recently logged record, enter “S” followed by 0 (zero) and then press Enter (i.e.
S0 <Enter>). To view earlier records in reverse chronological order, enter S and
press Enter. To go back 200 or 700 records, enter S200 or S700, etc. and
press Enter.
9.4.3
Sensor Log
The sensor values can be logged at a different rate if needed by setting the Sensor Log Interval in
the Diagnostics Menu. The log interval can vary from once every minute to once every day. Table 9-
3 shows a sample Sensor Log every 5 minutes for a boiler running in Constant Setpoint mode.
Table 9-1. Sample Fault Log Display
No.
Fault Message
Cycle
Date
Time
0
Direct Drive Signal Fault
609 1/10/02 8:42am
1
Low Gas Pressure
366 7/04/01 5:29pm
2
Loss of Power
0 1/01/01 11:50am
Table 9-2. Sample Operation Time Log Display
Status
Fire Rate
Flame
Run Length
Date
Time
Off, Direct Drive
0
0
8
1/15/02
2:35pm
Run, Direct Drive
38
100
34
1/15/02
2:27pm
Run, Direct Drive
31
100
30
1/15/02
1:53am
Run, Direct Drive
35
100
2
1/15/02
1:23pm
Run, Direct Drive
29
100
0
1/15/02
1:21pm
Ignition
0
0
0
1/15/02
1:20pm
Off, Switch
0
0
35
1/15/02
12:30pm
Run, Manual
40
100
0
1/15/02
11:55am
Ignition
0
0
0
1/15/02
11:55am
Power-up
0
0
0
1/15/02
11:50am
Table 9-3. Sample Sensor Log Display
Setpt Outlet Outdr
FFWD
Aux
Inlet
Exhst
CO
O2
Flow
Date
Time
130
181
OPEN OPEN
OPEN OPEN OPEN 0
.0
0
1/15/02 5:51pm
130
180
OPEN OPEN
OPEN OPEN OPEN 0
.0
0
1/15/02 5:46pm
130
180
OPEN OPEN
OPEN OPEN OPEN 0
.0
0
1/15/02 5:41pm
130
179
OPEN OPEN
OPEN OPEN OPEN 0
.0
0
1/15/02 5:36pm
130
180
OPEN OPEN
OPEN OPEN OPEN 0
.0
0
1/15/02 5:31pm
130
180
OPEN OPEN
OPEN OPEN OPEN 0
.0
0
1/15/02 5:26pm
130
180
OPEN OPEN
OPEN OPEN OPEN 0
.0
0
1/15/02 5:21pm
130
180
OPEN OPEN
OPEN OPEN OPEN 0
.0
0
1/15/02 5:16pm
130
179
OPEN OPEN
OPEN OPEN OPEN 0
.0
0
1/15/02 5:11pm
130
180
OPEN OPEN
OPEN OPEN OPEN 0
.0
0
1/15/02 5:06pm