CHAPTER 3
OPERATION
PR1: 10/18//12 AERCO International Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
•
Ph: 800-526-0288
Page 37 of 166
GF-120
OMM-0041 0E
Benchmark 1.5LN Low NOx Boiler
Installation, Operation and Maintenance Manual
NOTE
The Outdoor Temp display item shown with an asterisk in Table 3-2 will not
be displayed unless the Outdoor Sensor function has been enabled in the
Configuration Menu (Table 3-4).
Table 3-2: Operating Menu
Available Choices or Limits
Menu Item Display
Minimum
Maximum
Default
Status Message
Active Setpoint
40°F
240°F
AIR Temp
-70°F
245°F
Outdoor Temp*
-70°F
130°F
Valve Position In
0%
100% Valve Position
Flame Strength
0%
100%
Run Cycles
0
999,999,999
Run Hours
0
999,999,999
Fault Log
0
19
0
3.5 SETUP MENU
The Setup Menu (Table 3-3) permits the operator to enter the unit password (159) which is
required to change the menu options. To prevent unauthorized use, the password will time-out
after 1 hour. Therefore, the correct password must be reentered when required. In addition to
permitting password entries, the Setup Menu is also used to enter date and time, units of
temperature measurements and entries required for external communication and control of the
unit via the RS-232 port. A view-only software version display is also provided to indicate the
current Control Box software version.